Mitsubishi Electronics Q25HCPU ユーザーズマニュアル

ページ / 236
 
 
 
8 - 5                                                                                                                                                       8 - 5 
MELSEC-Q
 
8   EMC AND LOW VOLTAGE DIRECTIVE 
 
8.1.4 Power supply module 
Always ground the LG and FG terminals after short-circuiting them. 
 
8.1.5 When using QA1S6   B type base unit 
(1)   Cable 
 
(a)   Earthing of shielded cable 
• Earth the shield of the shielded cable as near the unit as possible taking 
care so that the earthed cables are not induced electromagnetically by the 
cable to be earthed. 
• Take appropriate measures so the shield that was partly removed for 
exposure is earthed to the control panel over a large contact surface area. 
A clamp may also be used as shown in the figure below. In this case, 
however, apply a cover to the painted inner wall surface of the control 
panel which comes in contact with the clamp. 
Shield section
 
Screw
Clamp fitting
Shielded cable
Paint mask
 
Note)  The method of earthing by soldering a wire onto the shield section of the 
shielded cable as shown below is not recommended. The high frequency 
impedance will increase and the shield will be ineffective. 
Shielded cable
Wire
Crimp terminal