5  Owner Maintenance
MIX 56 User Manual
5-12
Telect, Inc. 122188-10 A0
A warning message appears, stating the standby card’s flash pro-
gram has been updated, and you must now switch to the standby 
card to activate a flash update to the currently active card.
6.
As the warning message instructs, press Esc to exit this screen.
The Update Flash screen reappears, and the message “***Flash up-
date successful***” appears on the TFTP Ethernet Port line.
7.
Go to the System Settings screen and make the standby card the ac-
tive card (see “Specifying System Settings & M13 Card Functions” 
on page 4-14).
When you do this, the auto-update feature of the software causes 
the former active card (now the standby card) to update to the new 
software from the former standby card (now the active card). When 
both cards have the same software version, the minor alarm clears.
Craft Port Update
Before beginning, ensure the two update files (internal flash and external 
flash) are on the terminal (or PC running terminal emulation software) con-
nected to the MIX 56 system.
NOTE
The Craft Port Update can be used on Redundant or Nonredundant Sys-
tems. You must also know the names of the files. These are available in the
download instructions at www.telect.com.
Step
Action
1.
From the Directory screen, type 10 to select Update Flash and 
press Enter.
The Update Flash screen appears.
2.
Tab to the [Serial Load] button and press Enter.
A prompt appears asking you to confirm updating the software.
3.
Type y and press Enter.
A screen appears asking you to download the external flash file.