Honeywell DCP552 Mark II ユーザーズマニュアル

ページ / 247
12  -  2
Calibration Procedures
Enter calibration mode
(1)
Release keylock.  (
PARA PA01=0
)
(2)
Press 
DISP key
to permit ordinary indication condition.
Change to READY (
RUN
and 
HLD
are off) and AUTO (
MAN
off) modes.
The following LEDs will illuminate after the above operations.
RUN
LED is OFF
HLD
LED is OFF
MAN
LED is OFF
Figure 12-2.
(3)
To enter calibration mode, hold down the 
FUNC key
, and press 
SETUP key
and 
ENTER key
simultaneously.
The display will show the symbols described in Figure 12-3.  If the indication
is different, repeat the above procedure after pushing 
DISP key
to refresh the
display.
(4)
To select individual calibration items, press 
keys
to select the
item by scrolling, then 
SETUP key
, and 
ENTER key
.
The order of calibration items is described in Table 12-2.
Figure 12-3.
FUNC
AT
SETUP
ENTER
A/M
PID
PARA
CLR
CARD
LOAD
SAVE
LOADER
CYC
OUT
DEV
PV
SP
TM
SYN
RUN
HLD
MAN
PRG
AT
BAT
EG1
EG2
PROG RUN/HOLD DISP
RESET
PROG
SEG
PROFILE
MESSAGE
MESSAGE
ADV
0.0.0.0.
A.d.J.S.
00
00



   
 
 
 
   !"#$%
 
&&'(   !"#$%
12-7
Chapter 12.  CALIBRATION