Mitsumi electronic LMAP03U ユーザーズマニュアル

ページ / 24
14
5-4 Test Run
Perform the test run according to the test procedure of the test run check list.
(1) Test run of units by local remote controller
* Confirm that all units are running normally.
(2) Test-operation of the indoor unit from LM ADAPTER
Turn on SW1-9 of LM ADAPTER.
Finally turn OFF SW1-9, and verify that all indoor units are stopped.
* If there is even one indoor unit that is not running,the LM ADAPTER may not correctly recognize the indoor unit.
  Refer to the next chapter “ Troubleshooting ”.
(3) Test-operation of the indoor unit from L
ON
W
ORKS
®
If there is any tool which corresponds to L
ON
W
ORKS
® 
,verify that it can be operated from 
 
L
ON
W
ORKS
®  
network according to
the follwing procedure.
 Set the LM ADAPTER in config .
If LM ADAPTER has been already bounded to another model (the service LED is not ON), don't apply any new binding.
During the test operation, use “ nv1n Reguest ON/OFF ” to verify that the indoor unit can be operated. 
For details of “ nv1n Reguest ON/OFF ” , refer to the following.
nv1n Request ON/OFF command input
This input network variable is used to allow On request or Off request of the indoor unit to be 
changed via the network.
When the ventilator (LOSSNAY) Interlocks with the indoor unit, it becomes the same operation as
the indoor unit.
Valid range (SW1-7 OFF)
value field: not used
state field: 0      = indoor unit or ventilator unit is “ OFF ”
state field: 1      = indoor unit or ventilator unit is “ ON ”
: Else = Indoor unit or ventilator unit is “ OFF ”
_n: ------------ Indoor unit address (M-NET)
* Refer to the index in the table below when performing update and poll (confirm state) of the 
  network variable for the L
ON
W
ORKS
®
 tools (nodeutil etc.).
ON/OFF Reguest
ON/OFF run state
nv name
nv name
Finally put the LM ADAPTER in the unconfig, and end the test operation.
Contact your dealer for details on trial operation from the L
ON
W
ORKS
®
 network.
Perform the test run of the units by using the local remote controller or system controller.
1
1
1
2
2
3
index
1
2
49
50
51
52
99
100
nviOnOff_001
nviOnOff_002
nviOnOff_049
nviOnOff_050
nvoOnOff_001
nvoOnOff_002
nvoOnOff_049
nvoOnOff_050
index
network input SNVT_switch nviOnOff_n;
:
:
:
: