Mitsumi electronic LMAP03U ユーザーズマニュアル

ページ / 24
17
(1)The LM ADAPTER is not completely 
initialized. 
(2)Setting on M-NET side is not properly 
completed.
(3)If system controller is used together 
LM ADAPTER is not registered to 
system controller.
(4)The independent/combined 
LOSSNAY of LM ADAPTER is not 
set.
(5)L
ON
W
ORKS
®
 network transmission 
wire is not properly connected.
(6)The termination of L
ON
W
ORKS
®
 
network is not properly set.
(7) Binding of L
ON
W
ORKS
®
 network is 
not properly ended.
Refer to 2-(1).
Refer to 2-(2).
Refer to 2-(3).
Refer to 3-(4).
Refer to 4-(4).
Refer to 4-(5).
Refer to 4-(6).
Error content
Cause
Checking method and remedy
Independent/combi
ned LOSSNAY can 
not be operated 
from the LON side.
(1)The LM-ADAPTER is not completely 
initialized. 
(2)Setting on M-NET side is not properly 
completed.
(3)If system controller is used together 
LM ADAPTER is not registered to 
system controller.
(4)L
ON
W
ORKS
®
 network transmission 
wire is not properly connected.
(5)The termination of L
ON
W
ORKS
®
 
network is not properly set.
(6) Binding of L
ON
W
ORKS
®
 network is 
not properly ended.
Refer to 2-(1).
Refer to 2-(2).
Refer to 2-(3).
Refer to 4-(4).
Refer to 4-(5).
Refer to 4-(6).
Air conditioner can 
not be operated 
from the LON side.
5
6
7
8
Prohibit local remote 
controller operation 
cannot be set from 
the LON side.
Forced thermo OFF 
cannot be set from 
the LON side.
(1) Perform the LM ADAPTER’S prohibit 
      local remote controller operation 
      setting.
(1) Perform the LM ADAPTER’S forced 
      thermo OFF setting.
Turn on SW1-8 of LM ADAPTER, and reset the power 
supply.
Turn on SW1-1 of LM ADAPTER, and reset the power 
supply.