App. - 1
 
 
APPENDIX 
Appendix 1    I/O Control Mode 
The CPU supports two types of I/O control modes; the direct mode and refresh 
mode. 
 
Appendix 1.1  Direct mode 
In the direct mode, input signals are imported to a programmable controller every 
time they are input and treated as input information. The operation results of a 
program are output to the output data memory and the output modules. The 
following diagram shows the flow of I/O data in the direct mode. 
 
Data memory for inputs (X)
Test operation using peripheral device
Link refresh of MELSECNET/H
Writing from serial communication 
modules, etc.
Data memory for outputs (Y)
Executing the OUT instruction in the 
sequence program
Test operation using peripheral device
Writing from serial communication 
modules, etc.
Programmable controller
CPU
(Operation processing)
Input 
module
Output 
module
Y70
X0
Y75
1)
2)
3)
4)
5)
 
 
• When the input contact instruction is executed:   
An OR operation is executed in the input information 1) from the input module and 
input information 2) in the data memory. Then the result is used as input 
information 3) at sequence program execution. 
• When the output contact instruction is executed:   
Output information 4) is read from the data memory for output (Y), and a sequence 
program is executed. 
• When the output OUT instruction is executed:   
The operation result 5) of the sequence program is output to the output module, 
and is stored in the data memory for output (Y). 
• When the QCPU executes I/O in the direct mode, a sequence program uses DX 
for inputs and DY for outputs.