Appendix 4.28    Program using digital switch to import data 
When a set value of the digital switch is always input and stored to D10 of the 
programmable controller 
 
1
2
3
4
Digital switch
Input module
CPU
X20
X2F
Data 
register
D10
to
Converted into BIN
BIN
K4X20
D10
SM400 (always ON)
Wrong 
configuration
 
 
In the above program, changing a value of the digital switch while the programmable 
controller is in RUN may cause codes other than 0 to 9 depending on the timing of 
the change, which may cause an operation error of the CPU. 
To avoid this, write a program as follows. 
 
(Example 1)  For 4 digits of X20 to X2F 
SM400
0
K1X20
K0
<=
K1M20
K1X20
MOV
K1M24
K1X24
MOV
K1M28
K1X28
MOV
K1M32
K1X2C
MOV
D10
K4M20
BIN
K1X24
K0
K1X28
K0
K1X2C
K0
K1X20
K9
>=
K1X24
K1X28
K1X2C
<=
<=
<=
K9
K9
K9
>=
>=
>=
 
 
(Example 2)  For 8 digits of X20 to X3F 
SM400
0
Z0
RST
K8
FOR
K1M100Z
K1X20Z
MOV
Z0
K4
+
NEXT
K1X20Z0
K0
K1X20Z0
<=
K9
>=
4
7
31
32
D10
K8M100
DBIN
K8Y40
D10
DBCD
SM400