4.3  Measuring Timer 
Project name 
QB-3 
Program name 
MAIN 
 
K30
Timer setting value (time limit: 3.0sec.)
T0
Y70
Y71
X5
T0
T0
0
5
7
 
 
*: OUT T is a 4-step instruction. 
 
[Timing chart] 
Contact X5
Coil T0
Normally open contact T0, 
coil Y70
Normally closed contact 0b, 
coil Y71
3.0sec.
 
•  The timer contact 
operates delaying by a set 
time after the coil is 
energized. (On delay 
timer) 
•  The timer setting range is 
from K1 to K32767. 
Low-speed (100ms) timer 
0.1 to 3276.7sec. 
High-speed (10ms) timer 
0.01 to 327.67sec. 
•  When the timer setting 
value is set to 0, it turns on 
(time-out) by the execution 
of the instruction. 
 
• The following four types of timer are available.   
 
Type 
Timer No. (default)
Low-speed 
timer·············
Counts time in 
units of 100ms.
High-speed 
timer·············
Counts time in 
units of 10ms. 
Default 
T0 to T2047 (2048)
Low-speed 
retentive 
timer·············
Accumulates 
time in units of 
100ms. 
High-speed 
retentive 
timer·············
Accumulates 
time in units of 
10ms. 
 
Default: 0 
 
The value can be 
changed using the 
parameter. 
 
•  Change the output 
instruction (OUT) to 
OUTH to select the 
high-speed timer or 
high-speed retentive timer.
•  To use the retentive timer, 
set the device points for 
the retentive timer in the 
device setting of the PLC 
parameter. 
 
Refer to section 6.4 for explanation on the retentive timers.