CHAPTER 9 TROUBLESHOOTING
9
9.3  C
hecking the LEDs
9.3.2  T
he LEDs on the 
CC-Link IE Field
 Networ
k pa
rt
9.3.2
The LEDs on the CC-Link IE Field Network part
(1) RUN LED
(a) When turned off
If the above action does not solve the problem, perform a unit test on the Ethernet adapter module to check for 
hardware failure. (
(b) When flashing
If the above does not solve the problem, perform a unit test on the Ethernet adapter module to check for 
hardware failure. (
Checking
Action
Is the Ethernet adapter module in execution of a unit test?
If the MODE LED is flashing, a unit test is being performed. Reset the 
Ethernet adapter module, or turn off the power and then on.
Checking
Action
Is the switch of the Ethernet adapter module set to RUN?
Set the switch of the Ethernet adapter module to RUN to start data link.
Is the module in the remote STOP status?
Cancel the remote STOP and start data link.
Is the master station in the RUN status?
Place the master station into the RUN state. If the master station has 
stopped due to an error, troubleshoot it referring to the manual for the 
master station. (
 User's manual for the master/local module used)
Was the Ethernet adapter module disconnected while the 
master station was in the STOP status?
• Place the master station into the RUN state, and reconnect the 
Ethernet adapter module to the network.
• Reset the Ethernet adapter module since it retains the STOP status 
data of the master station.