CHAPTER 9 TROUBLESHOOTING
9
9.4 T
roubleshooting by Symptom
9.4.7 C
ommunications ca
nnot be per
formed u
sing the IP pa
cket tran
sfer
function
function
9.4.7
Communications cannot be performed using the IP packet
transfer function
transfer function
Before troubleshooting the problem as listed below, execute the IP communication test and take corrective actions
according to the error code. (
If the problem cannot be solved using the IP communication test, execute the actions listed below.
Checking
Action
Does the Ethernet adapter module support the IP packet
transfer function?
transfer function?
• Check that bit 1 of Function check area of the own station (buffer memory
address: 48 (30
H
)) is on.
• Check that the serial number (first five digits) of the Ethernet adapter module
is 14022 or later.
(
When the IP address of the Ethernet adapter module
(Ethernet part) is the same as the network address of the
master station, is the IP address (the third and fourth
octets) of the external device and Ethernet adapter
module (Ethernet part) within the setting range?
(Ethernet part) is the same as the network address of the
master station, is the IP address (the third and fourth
octets) of the external device and Ethernet adapter
module (Ethernet part) within the setting range?
• Set the IP address that meets the rules described on Page 106, Section
7.3.1 (1) in the external device and Ethernet adapter module (Ethernet part).
• Change the IP address of CC-Link IE Field Network in the master station so
that the IP address of the external device and Ethernet adapter module
(Ethernet part) differs from the network address of the master station.
(Ethernet part) differs from the network address of the master station.
Is the IP address already in use?
• For the external device, set the IP address different from that of other
devices on the network, such as a CPU module, master/local module, and
Ethernet adapter module.
Ethernet adapter module.
• Disconnect the external device from the line and execute the Ping command
to the IP address of the disconnected external device. If a response is
received even though the external device is disconnected, the IP address is
already in use. Change the IP address.
received even though the external device is disconnected, the IP address is
already in use. Change the IP address.
Has a timeout error occurred in the IP communication
test?
test?
Check “Relay Network No.” in the routing parameters of the master station and
local stations.
local stations.
Have the routing parameters correctly been set in the
master station and local stations?
master station and local stations?
• Check and correct the routing parameters of the master station and local
stations.
• When the first and second octets of the IP address are the same for the
request source external device, request destination external device, and
modules between them, set the routing parameters so that the third octet of
the IP address of the external device is used as "Target Network No.".
modules between them, set the routing parameters so that the third octet of
the IP address of the external device is used as "Target Network No.".
• If a timeout error occurs in the IP communication test, enter the IP address
in the order of station from the closest to the device where the IP
communication test was executed. Repeat the test until which station can or
communication test was executed. Repeat the test until which station can or
cannot receive communications to identify the error. (
Section 7.3.6 (2) (b))
If the station causing the error is found, check and correct the settings.
If the station causing the error is found, check and correct the settings.
Is the network number of the external device side (the
third octet of the IP address) the same as that of modules
and another external device? (This applies only when the
request source external device, request destination
external device, and modules between them have the
same first and second octets of the IP address.)
third octet of the IP address) the same as that of modules
and another external device? (This applies only when the
request source external device, request destination
external device, and modules between them have the
same first and second octets of the IP address.)
Change the network number of the external device side (the third octet of the
IP address) to the one different from that of modules and another external
device.
IP address) to the one different from that of modules and another external
device.
Master station
Station No.1
Station No.2
Network No.1
Network No.
3
Network No.
2
192.168.
3
.1
192.168.
2
.1
192.168.
3
.30
192.168.
2
.30
192.168.1.1
(Automatically assigned)
192.168.1.125
192.168.1.2
(Automatically assigned)
Ethernet
CC-Link
IE Field
Network
IE Field
Network
IP address
Change the network numbers to those not used for other stations.