Multi-Tech Systems 7600 ユーザーズマニュアル

ページ / 372
ION 7500 / ION 7600 User’s Guide
Logging and Recording Capacity
Chapter 5 - Features and Applications 
Page 151
External ION Events
Some events are not produced by a specific module; they are generated internally 
by the meter. These events and their associated priority levels are shown in the 
table below.
Logging and Recording Capacity
The meter provides both data and event logs, but the amount of memory required 
to store these logs depends on the number of parameters being logged and the 
frequency with which these parameters are logged. The following equation can 
help determine the amount of memory required to store data and event logs:
each record consumes (in Bytes) = ((number of parameters * 5) + 8) 
The meter can also perform waveform recording. It can simultaneously capture 
events on all channels to a maximum of 96 cycles each. To calculate the waveform 
memory usage use the following formula:
waveform memory usage (in Bytes) = (2*(number of samples per cycle) + 
10)*(number of cycles in waveform) + 30 
N
OTE
Round up to the next kilobyte after each of the above calculations.
Event Group
Description
Priority Number
Warning
Factory initialize performed
30
Firmware or memory upgrade performed
Meter power-up or power-down
Internal modem not responding or modem recovered
Battery low
Telnet or serial terminal locked out
Security disabled or enabled
Failure
Communications fail to allocate required memory
255