Multi-Tech Systems 7600 ユーザーズマニュアル

ページ / 372
Security Setup
 ION 7500 / ION 7600 User’s Guide
Page 44
Chapter 2 - Using The Front Panel 
User Resets
This sub-menu contains less critical and user-configurable controls. 
DIST
 
COUNT
 
RESET
The meter contains a voltage disturbance display in its Power Quality Vista 
diagram, which counts the number of sag/swell events that have occurred since 
power-up or last reset. The Disturbance Count Reset allows you to clear this 
counter. See “PQ (Power Quality) Setup” on page 39.
MAN
 
WFM
 
TRG
The Manual Waveform Trigger forces the meter to perform a waveform capture. 
Waveform data is accessible in the Vista Power Quality diagram.
AVAILABILITY
 
RESET
This item resets the Power Availability framework. Current values in the 
Availability display screen - availability (up-time in parts per million), number of 
nines, and evaluation time (in days). The previous statistics will appear in the 
Previous Availability display screen.
EN
50160
 
RESET
 (ION 7600 only)
This item will reset all EN50160 parameters and statistics accumulated in the 
meter. Refer to Chapter 2 for a description of the EN50160 parameters displayed 
on the default front panel data screens and Vista diagrams. The technical note 
Power Quality: ION Meters and EN50160 contains more information about EN50160.
CUSTOM
 1 
TRIG
CUSTOM
 2 
TRIG
These are resets that you may program yourself with Designer. The ION 7600 only 
has the 
CUSTOM
 1 
TRIG
 available, whereas the ION 7500 has both custom resets. 
Security Setup
The meter’s eight-digit password allows you to configure the meter using the 
meter’s front panel. 
The settings in Security menu item allow you to: 
modify the existing meter password 
disable the password security check
disable web browser configuration of the meter  
You require the valid password to enter this menu. The default password is 0 
(zero).
N
OTE
The password enables users to change the configuration of the meter. It is recommended that you change
your password from the default when you put the meter into service.