Multi-Tech Systems 7600 ユーザーズマニュアル

ページ / 372
ION 7500 / ION 7600 User’s Guide
Display Setup
Chapter 3 - Default Meter Functionality 
Page 63
Display Setup
The meter’s front panel display is controlled by three types of ION modules: the 
Display Options module, the Scroll module, and Display modules.
Display Options Module Settings
The Display Options module contains setup registers that hold data display 
settings such as contrast level, backlight timeout, daylight savings time, and 
update time. Settings in the Display Options modules are global, and affect the 
entire set of front panel display screens.
Scroll Module Settings
The Scroll module determines the sequence and rate of scrolling for multiple front 
panel display screens.
The Trigger outputs of Scroll module are linked to the inputs of Display modules. 
When a pulse is sent from the Trigger output of a Scroll module to a linked Display 
module, the Display module shows its information on the front panel.
Display Module Settings
Display modules determine the form and content of each display screen
.
Setup Register
Function
Default
Contrast
Sets the global contrast setting for the meter display.
7
Backlight Timeout
Sets the time that the front panel’s backlight stays on after the last press of a front 
panel button (in seconds).
300
Display Update Time
Sets the period between data display refreshes (in seconds).
1
Digital Grouping
Sets the numbering format by determining how groups of three digits are 
separated.
1,000
Demand Lockout Timeout
Sets the minimum time allowed between consecutive demand resets.
2,160,000
Setup Register
Function
Default
Scroll Delay
Sets the time that will elapse between successive pulses on the 
Trigger
 outputs when the 
scroll module is enabled.
6
Wraparound
Designates the last 
Trigger
 output (
Trigger
 n) before returning to the first 
Trigger 
in 
he order.
10
Freeze Time
Sets the time (in seconds) that the Scroll module remains "frozen" when pulsed from the 
Freeze
Up
, or 
Down
 inputs.
120
Setup Register
Function
Default
Screen Type
This specifies the way the linked parameters are displayed on the front panel 
screen.
Defaults vary among display 
screens. Refer to the 
ION 
Device Templates
 at 
www.pwrm.com.
Softkey Number
This assigns a softkey number to the display screen.
Softkey Name
This assigns a softkey name to the display screen.
Screen Title