Mitsubishi Electronics A1SJ71AT23BQ ユーザーズマニュアル

ページ / 158
3
 - 15
3.5 Buffer Memory List
 
3
SPECIFICATIONS
3.5
Buffer Memory List
The following shows a buffer memory list of a local module.
Table 3.10 Buffer memory list
Address
Name
Initial 
value
Readable/
Writable*
1
Reference 
section
Hexadecimal
Decimal
0
H
 to 1
H
0 to 1
Presence or absence of refresh information table
0
R
2
H
2
Refresh information 
table (First half of link 
parameters)
Host station send 
range of W
Start number (0 to FFF)
3
H
3
Points (in units of words)
4
H
4
Other station send 
range (1) of W
Start number (0 to FFF)
5
H
5
Points (in units of words)
6
H
6
Other station send 
range (2) of W
Start number (0 to FFF)
7
H
7
Points (in units of words)
8
H
8
Host station send 
range of B
Start number (0 to FF0)
9
H
9
Points (in units of words)
A
H
10
Other station send 
range (1) of B
Start number (0 to FF0)
B
H
11
Points (in units of words)
C
H
12
Other station send 
range (2) of B
Start number (0 to FF0)
D
H
13
Points (in units of words)
E
H
14
Host station send 
range of Y
Start number (0 to 7F0)
F
H
15
Points (in units of words)
10
H
16
System area (Use prohibited)
-
-
-
11
H
17
Host station receive 
range of X
Start number (0 to 7F0)
0
R
12
H
18
Points (in units of words)
13
H
19
System area (Use prohibited)
-
-
-
14
H
20
Refresh information 
table (Latter half of 
link parameters)
Host station send 
range of W
Start number (0 to FFF)
0
R
15
H
21
Points (in units of words)
16
H
22
Other station send 
range (1) of W
Start number (0 to FFF)
17
H
23
Points (in units of words)
18
H
24
Other station send 
range (2) of W
Start number (0 to FFF)
19
H
25
Points (in units of words)
1A
H
26
Host station send 
range of B
Start number (0 to FF0)
1B
H
27
Points (in units of words)
1C
H
28
Other station send 
range (1) of B
Start number (0 to FF0)
1D
H
29
Points (in units of words)
1E
H
30
Other station send 
range (2) of B
Start number (0 to FF0)
1F
H
31
Points (in units of words)
20
H
32
Refresh information 
table (Send range of 
master station for the 
second tier)
Send range of 
master station for 
second tier (first 
half) of W
Start number (0 to FFF)
21
H
33
Points (in units of words)
22
H
34
Send range of 
master station for 
second tier (first 
half) of B
Start number (0 to FF0)
23
H
35
Points (in units of words)
24
H
36
Send range of 
master station for 
second tier (latter 
half) of W
Start number (0 to FFF)
25
H
37
Points (in units of words)
26
H
38
Send range of 
master station for 
second tier (latter 
half) of B
Start number (0 to FF0)
27
H
39
Points (in units of words)