9   MAJOR POSITIONING CONTROL 
 
9.2.19 Current value changing 
When the current value is changed to a new value, control is carried out in which the 
"
Md.20
 Current feed value" of the stopped axis is changed to a random address set 
by the user. (The "
Md.21
 Machine feed value" is not changed when the current value 
is changed.) 
 
The two methods for changing the current value are shown below.  
[1]  Changing to a new current value using the positioning data 
[2]  Changing to a new current value using the start No. (No. 9003) for a current 
value changing 
 
The current value changing using method [1] is used during continuous positioning of 
multiple blocks, etc.  
 
[1]   Changing to a new current value using the positioning data 
 
 Operation chart 
 
The following chart shows the operation timing for a current value changing. The 
"
Md.20
 Current feed value" is changed to the value set in "
Da.6
 Positioning 
address/movement amount" when the positioning start signal turns ON. 
 
Positioning start signal
[Y10,Y11,Y12,Y13]
Md.20
50000
0
OFF
ON
Current feed value changes to the 
positioning address designated by the
positioning data of the current value changing.
The above chart shows an example
when the positioning address is "0".
Current feed value
 
 
 Restrictions 
 
(1)  An axis error "New current value not possible (error code: 515)" will occur and 
the operation cannot start if "continuous path control" is set in "
Da.1
 
Operation pattern". ("Continuous path control" cannot be set in current value 
changing.) 
 
(2)  "Current value changing" cannot be set in "
Da.2
 Control system" of the 
positioning data when "continuous path control" has been set in "
Da.1
 
Operation pattern" of the immediately prior positioning data. (For example, if 
the operation pattern of positioning data No. 1 is "continuous path control", 
"current value changing" cannot be set in positioning data No. 2.) An axis error 
"New current value invalid (error code: 515)" will occur and the machine will 
carry out a deceleration stop if this type of setting is carried out.  
 
(3)  An axis error "Outside new current value range (error code: 514)" will occur 
and the operation cannot start if "degree" is set in "
Pr.1
 Unit setting" and the 
value set in "
Da.6
 Positioning address/movement amount (0 to 359.99999 
[degree])" is outside the setting range.