10 - 15 
MELSEC-Q
 
10   HIGH-LEVEL POSITIONING CONTROL 
 
10.3.8 Restrictions when using the NEXT start 
The "NEXT start" is a instruction indicating the end of the repetitions when executing 
Section 10.3.6 "Repeated start (FOR loop)" and Section 10.3.7 "Repeated start (FOR 
condition)".  
 
The following shows the restrictions when setting "6: NEXT start" in the " block start 
data".  
 
(1)  The processing when "6: NEXT start" is set before execution of "4: FOR loop" or 
"5: FOR condition" is the same as that for a "0: block start".  
 
(2)  Repeated processing will not be carried out if there is no "6: NEXT start" 
instruction after the "4: FOR loop" or "5: FOR condition" instruction. (Note that an 
"error" will not occur.) 
 
(3)  Nesting is not possible between "4: FOR loop" and "6: NEXT start", or between 
"5: FOR condition" and "6: NEXT start". A warning "FOR to NEXT nest 
construction (warning code: 506)" will occur if nesting is attempted.  
 
Block start data 
 Da.13   
Special start instruction 
 
 
1st point 
Block start 
 
 
2nd point 
FOR 
 
 
3rd point 
Block start 
 
 
4th point 
FOR 
5th point 
Block start 
6th point 
Block start 
7th point 
NEXT 
8th point 
Block start 
9th point 
NEXT 
 
 
 
 
The JUMP destination of the
NEXT designated with points
7 and 9 is the FOR of point 4.
A warning will occur if the NEXT
designated with point 9 is
executed.