12   CONTROL SUB FUNCTIONS 
 
12.4 Functions to limit the control 
Functions to limit the control include the "speed limit function", "torque limit function", 
"software stroke limit function", "hardware stroke limit function", and "forced stop 
function". Each function is executed by parameter setting or PLC program creation and 
writing. 
 
12.4.1 Speed limit function 
The speed limit function limits the command speed to a value within the "speed limit 
value" setting range when the command speed during control exceeds the "speed limit 
value".  
 
The details shown below explain about the "speed limit function".  
  [1] Relation between the speed limit function and various controls 
  [2] Precautions during control 
  [3] Setting the speed limit function 
 
[1]   Relation between the speed limit function and various controls 
The following table shows the relation of the "speed limit function" and various 
controls.  
 
Control type 
Speed limit function  Speed limit value 
Machine OPR control 
 
OPR 
control 
Fast OPR control 
 
1-axis linear control 
 
2 to 4-axes linear 
interpolation control 
 
1-axis fixed-feed control 
 
2 to 4-axes fixed-feed 
control (interpolation) 
 
Position 
control 
2-axis circular interpolation 
control 
 
1 to 4-axes Speed control 
 
Speed-position switching control, 
Position-speed switching control 
 
Pr.8
Speed limit 
value 
Current value changing 
– 
Major 
positioning 
control 
Other 
control 
JUMP instruction, NOP 
instruction, LOOP to 
LEND 
– 
Setting value invalid 
JOG operation, Inching operation 
 
Pr.31
JOG speed 
limit value 
Manual 
control 
Manual pulse generator operation 
– 
Setting is invalid 
 
 : Always set 
–  :  Setting not required (Setting value is invalid. Use the initial values or setting values 
within a range where no error occurs.)