Mitsubishi Electronics QD75MH2 ユーザーズマニュアル

ページ / 838
 
 
 
12 - 79 
MELSEC-Q
 
12   CONTROL SUB FUNCTIONS 
 
12.7.5 Target position change function 
The "target position change function" is a function to change a target position to a 
newly designated target position at any timing during the position control (1-axis linear 
control).  A command speed can also be changed simultaneously. 
The target position and command speed changed are set directly in the buffer 
memory, and the target position change is executed by "
Cd.29
Target position 
change request flag". 
 
The following shows the details of the "target position change function". 
[1] Details of control 
[2] Precaution during operation 
[3] Method of setting target position change function from PLC CPU 
 
[1]   Details of control 
The following charts show the details of control of the target position change 
function. 
 
(a) When the address after change is positioned away from the start point more than the positioning address: 
Target position change request
Positioning address
Address after change
V
t
 
(b) When the speed is changed simultaneously with changing the address: 
Target position change request
Positiioning address
Address after change
Speed before
change
Speed after
change
V
t
 
(c) When the direction of the operation is changed: 
Target position change
request
Positioning address
Address after
change
V
t
 
Fig. 12.41 Target position change operation