Mitsubishi Electronics QSPCU ユーザーズマニュアル

ページ / 224
9
EMC, LOW VOLTAGE, AND MACHINERY DIRECTIVES
9.1 Requirements for Conformance to EMC Directive
9.1.1 Standards relevant to the EMC Directive
9
 - 2
9
EM
C AN
D
 L
O
V
O
LT
AG
DI
RE
C
T
IV
E
S
10
LO
A
D
ING A
ND 
INS
TA
LLA
T
ION
11
M
A
INT
E
NANCE
 AND 
IN
SP
ECT
IO
N
12
T
R
O
U
BL
ES
HO
O
T
IN
G
 A
PPE
NDICES
 INDEX
 
 
9.1.1  Standards relevant to the EMC Directive
(1) Emission related standards
 * 1 : QP: Quasi-Peak value, Mean: Average value
 * 2 : Programmable controller is an open type device (a device designed to be housed in other 
equipment) and must be installed inside a conductive control panel. The tests were conducted 
with the programmable controller installed in a control panel, applying the maximum applicable 
input voltage to the power supply module.
(2) Immunity related standards
 * 1 : Programmable controller is an open type device (a device designed to be housed in other 
equipment) and must be installed inside a conductive control panel. The tests were conducted 
with the programmable controller installed in a control panel, applying the maximum applicable 
input voltage to the power supply module.
 * 2 : The accuracy of an analog-digital converter module may temporarily vary within ±10%.
Table9.1 Emission related standards
Standard
Test item
Test description
Value specified in standard
EN61131-2: 
2007
CISPR16-2-3
Radiated emission
*2
The electromagnetic wave which 
the product emits to the external 
space is measured.
• 30 to 230MHz, QP: 40dBµV/m (measured at 10m 
distance)
*1
• 230 to 1000MHz, QP: 47dBµV/m (measured at 
10m distance)
CISPR16-2-1, 
CISPR16-1-2
Conducted emission
*2
The noise level which the product 
emits to the power line is 
measured.
• 0.15 to 0.5MHz, QP: 79dB, 
Mean: 66dB 
*1
• 0.5 to 30MHz, QP: 73dB, Mean: 60dB
Table9.2 Immunity related standards
Standard
Test item
Test description
Value specified in standard
EN61131-2: 
2007
EN61000-4-2
Electrostatic discharge 
immunity
*1
An electrostatic discharge is 
applied to the enclosure of the 
equipment.
• 8kV   Air discharge
• 4kV   Contact discharge
EN61000-4-3
Radiated, radio-frequency, 
electromagnetic field 
immunity
*1
An electric field is radiated to the 
product.
80% AM modulation @1kHz
• 80 to 1000MHz: 10Vm
• 1.4 to 2.0GHz: 3Vm
• 2.0 to 2.7GHz: 1Vm
EN61000-4-4
Fast transient burst 
immunity
*1
Burst noise is applied to power 
lines and signal lines.
• AC/DC power, I/O power, and AC I/O (unshielded) 
lines: 2kV
• DC I/O, analog, and communication lines: 1kV
EN61000-4-5
Surge immunity
*1
Lightning surge is applied to 
power lines and signal lines.
• AC power, AC I/O power, and AC I/O (unshielded) 
lines: 2kV CM, 1kV DM
• DC power and DC I/O power lines: 0.5kV CM, 
0.5kV DM
• DC I/O, AC I/O (shielded), analog
*2
, and 
communication lines: 1kV CM
EN61000-4-6
Conducted RF immunity
*1
High-frequency noise is applied 
to power lines and signal lines.
0.15 to 80MHz, 80% AM modulation @1kHz, 10Vrms
EN61000-4-8
Power-frequency magnetic 
field immunity
*1
The product is immersed in the 
magnetic field of an induction 
coil.
50/60Hz, 30A/m
EN61000-4-11
Voltage dips and interruption 
immunity
Power voltage is momentarily 
interrupted.
• 0%, 0.5 period, starting at zero-crossing
• 0%, 250/300 period (50/60Hz)
• 40%, 10/12 period (50/60Hz)
• 70%, 25/30 period (50/60Hz)