Mitsubishi Electronics 700 Series ユーザーズマニュアル

ページ / 183
9
Function Block Diagram
1
1.5.5
Setting list of built-in PLC function parameter
The built-in PLC function parameters are designed to specify the ranges of using the
PLC function, e.g. program capacity, device assignment and various functions.
Item
GX Developer Default
Setting Range
<Usable device range>
Sequence program 
capacity
6k steps
1k step
File register capacity
None
Cannot be set (default)
Comment capacity
None
Cannot be set (default)
Status latch
None
Cannot be set (default)
Sampling trace
None
Cannot be set (default)
Microcomputer program 
capacity
None
Cannot be set (default)
Latch range setting
L1000 to L2047
Cannot be set (invalid if set)
Link range setting
None
Cannot be set (default)
I/O assignment
None
Cannot be set (default)
Internal relay, latch relay, 
step relay setting
M0 to 999
L1000 to 2047
None for S
L and S cannot be set.
(Operates as M if set)
<M0 to M63>
Watchdog timer setting
200ms
10 to 2000ms
Timer setting
100ms: T0 to 199
10ms: T200 to 255
(100ms timers since only T0 to 7 
are available)
16 points for 100ms, 10ms and 
retentive timers. Timers have 
consecutive numbers.
<T0 to T15>
Counter setting
Without interrupt counters
Cannot be set (default)
<C0 to C15>
Remote run/pause
None
Can be set using X0 to 1F. 
Otherwise invalid. Pause does not 
function.
Error-time operation mode
Fuse blow: Continued
Setting invalid (since there are no 
fuses)
I/O verify error: Stop
Setting invalid 
(since there are no I/O modules)
Operation error: Continued
Stop/Continued
Special function module check 
error: Stop
Setting invalid (since there are no 
special modules)
STOP 
→ RUN output mode
Operation status prior to 
STOP is re-output.
Prior to STOP/after operation 
execution
Print title registration
None
Cannot be set
Keyword registration
None
Online setting cannot be made but 
parameter setting is valid.
REMARKS
•The following functions are not supported.
1. Constant scan, 2. Latch (device data backup for power failure), 3. Pause, 
4. Status latch, 5. Sampling trace, 6. Offline switch
•If parameter clear of the inverter is performed, the above built-in PLC function parameters are
not cleared.
•For the built-in PLC function parameter setting operation, refer to the GX Developer
Operating Manual.