How to Read the Error Code
When the built-in PLC function is in the RUN status or if an alarm occurs during RUN,
the self-diagnostic function displays the error and stores the error code and error step
into the special registers. This chapter describes the error definitions and corrective
actions.
4.1 How to Read the Error Code
When an error has occurred, the error code can be read with the peripheral device.
For the operation method, refer to the operating manual of the peripheral device.
The following table indicates the error names, error codes, definitions, causes and
corrective actions.
The error code and error step are stored into the following special registers.
Error code................. D9008
Error step.................. D9010, D9011
Table 4.1 Error Code List
Error Name
Error 
Code
(D9008)
Status
Definition and Cause
Corrective Action
“INSTRCT 
CODE ERR.”
[Checked at 
instruction
execution]
10
Stop
The instruction code that 
cannot be decoded is 
included in the program.
 The memory contents 
changed for some reason.
Read the error step using 
GX Developer, and correct 
that step in the program.
“PARAMETER 
ERROR”
[Checked at 
power-on or 
STOP to RUN]
11
Stop
(1) Write to the CPU was 
performed after the 
capacity larger than the 
memory capacity of the 
CPU was set using GX 
Developer.
(2) The parameter data of the 
CPU memory changed 
due to noise or memory 
loading fault.
Check the memory capacity 
of the CPU with the 
memory capacity set using 
GX Developer, and re-set 
using GX Developer.
“WDT ERROR”
[Checked at 
END processing 
execution]
22
Stop
The scan time exceeds the 
watchdog error monitor time.
 The user program scan 
time has increased.
Calculate/check the user 
program scan time and 
reduce the scan time.
“END NOT 
EXECUTE”
[Checked at 
END instruction 
execution]l
24
Stop
(1) The END instruction has 
been read as another 
instruction code due to 
noise, etc.
(2) The END instruction has 
changed into another 
instruction code for some 
reason.
Reset and RUN again. If 
the same error appears 
again, the cause is a CPU 
hardware fault. Consult the 
Mitsubishi representative.