CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 
APC Symmetra LX 
 
GUIDE SPECIFICATIONS FOR  
4kVA-16kVA  
Uninterruptible Power System 
PART 1 - GENERAL 
1.1 
SUMMARY 
A. 
This specification describes the operation and functionality of a continuous duty, single-
phase, solid-state, static Uninterruptible Power System (UPS) hereafter referred to as 
the UPS. 
B. 
The UPS shall utilize modular power protection technology designed to allow internal 
redundancy, scalability of power and runtime, and fast mean time to repair (MTTR). 
The UPS should be configured from five basic components- UPS frames, extended run 
battery frames (XR frames), power modules, battery modules, and intelligence modules.  
UPS and XR frames should be capable of shipping with modules installed.  XR frames 
should be capable of communicating battery and runtime status to intelligence modules.  
Power, battery, and intelligence modules should be hot-swappable and user-replaceable 
for fast MTTR. 
C. 
Configuration Specifics:  
 
1. 
The UPS frame(s) should be capable of the following configurations: 
 
               
____4-8kVA N+1 Redundant Tower 
 
____4-16kVA N+1 Redundant Tower 
 
____4-16kVA N+1 Redundant Tower with nine (9) extra Battery Module slots 
 
____4-8kVA N+1 Redundant 13U Rack-mount 
 
____4-16kVA N+1 Redundant 19U Rack-mount 
 
2. 
The system power train shall be comprised of hot-swappable, user-replaceable 
3.2kW/4kVA and 10% Battery charger circuit power modules, which shall 
operate in parallel, and be configurable for N+1 redundant operation at rated 
load.     
 
3. 
The system shall also include a field-replaceable internal automatic and manual 
bypass system module, field-replaceable output power distribution panels, 
removable input/output wiring tray, standard redundant intelligent modules, 
battery disconnects, an LCD interface display, EPO, and an integrated UPS 
network management card with temperature monitoring. 
D. 
In addition, this specification describes the performance, functionality, and design of 
the UPS Service Bypass Panel, hereafter referred to as the SBP, the external Battery 
Systems, and connectivity solutions.