Honeywell 272630D ユーザーズマニュアル

ページ / 4
The 272630D provides: 
1.  A 2-10 Vdc voltage proportional to the valve 
stem position. This output is capable of 
sourcing up to 20 mA dc drive current. 
2. An isolated "Form C" relay contact closure 
that energizes when the valve is open more 
than the setting of the trimmer potentiometer 
("trim pot"). 
Position feedback voltage mirrors the control 
signal. For ML6984 and direct acting ML7984 
operation, see Fig. 3. For reverse acting 
ML7984, see Fig. 4. 
1.75V 
2.5V 
9.5V 
10.25V 
FEEDBACK VOLTAGE 
LOWER 
SEAT 
UPPER 
SEAT 
STROKE 
28 steps @ 
0.25V per step 
First and last steps 
are @ 0.75V per step 
Fig. 3 - Feedback voltage reponse for  
ML6984 and direct acting ML7984  
STROKE 
10.25V
9.5V
2.5V
1.75V 
FEEDBACK VOLTAGE 
LOWER 
SEAT 
UPPER 
SEAT 
28 steps @ 
0.25V per step 
First and last steps 
are @ 0.75V per step 
Fig. 4 - Feedback voltage response for 
reverse acting ML7984 
Auxiliary Switch Setup 
1. Drive actuator to desired position. 
2.  Adjust trimmer potentiometer ("trim pot") until 
relay is energized. (On-board LED will light).