Module
- Note down the Kp value that has been set as the critical proportional coefficient.
- Specify the duration of a complete oscillation as Tkrit, perhaps with a stop watch by generating the
arithmetical mean over several oscillations.
- Multiply the values of Kp,krit and Tkrit with the multipliers according to the table, and thus set the
determined values for Kp, Tn and Tv at the controller.
0.50
0.45
0.59
0.85
0.50
0.12
Preface Fundamentals Discontinuous Action Controller Controller Block (S)FB41 Setting the System Appendix
B3
Issued: 02/2008 Control Engineering with STEP 7