Series 90–70 Remote I/O Scanner User’s Manual – July 1992
118
PLC Fault Table at the Series 90–70 PLC
If the programmer is communicating with a Series 90–70 PLC and a remote drop fault
occurs, the PLC Fault Table shows the Drop ID and the rack and slot within the remote
drop where the fault has occurred:
33#0.1
Drop ID
Rack
Slot
Slot 1 is occupied by the Remote I/O Scanner.
Remote Drop Fault
  
Drop ID#, rack, slot
PLC Fault
  
rack, slot, bus, 
  bus address
|PROGRM |TABLES |
STATUS
 |       |       |LIB    |SETUP  |FOLDER |UTILTY |PRINT
1
plcrun
 2
passwd
 3
plcflt
 4
io flt
 5
plcmem
 6
blkmem
 7
refsiz
 8
sweep
  9
clear
 10
zoom
 
>                                                                               
                           P L C   F A U L T   T A B L E
 
                               
 TOP FAULT DISPLAYED: 0001                    TABLE LAST CLEARED: 09–21 08:00:00
        TOTAL FAULTS: 0002                    ENTRIES OVERFLOWED: 0000          
                                                  PLC DATE/TIME: 10–14 10:05:13 
 
     FAULT                          FAULT                         DATE    TIME
   LOCATION                       DESCRIPTION                     M–D  H: M: S 
 ___________ ___________________________________________________ _____ ________
   0.1       ADDITION OF DEVICE                                  10–13 08:12:22
   0.2.1.14  LOSS OF, OR MISSING OPTION MODULE                   10–13 09:50:14
   0.3.1.3   GENIUS BLOCK MODEL NUMBER MISMATCH                  10–13 11:04:15
   
33#0.1    I/O FAULT TABLE FULL                                10–14 16:27:54
 MAINPLC     RUN/ENABLE    7MS SCAN  ONLINE  L4 ACC: WRITE CONFIG CONFIG EQUAL
 PLC C: LESSON                  PRG: LESSON  
 REPLACE
Fault Clearing
Pressing the Clear key from this display clears the entire PLC Fault Table. If there are 
no
faults in the I/O Fault Table, then pressing Clear will also clear Remote I/O Scanner
faults.