Mitsumi electronic FR-CV-H7.5K to H30K(-AT) ユーザーズマニュアル

ページ / 63
12
Wiring
2.2 Wiring
2.2.1
Terminal connection diagram
Be sure to connect terminal RDY of the FR-CV to the X10 or MRS signal assigned terminal of the 
inverter, and connect terminal SE of the FR-CV to terminal SD of the inverter. Without proper 
connecting, FR-CV will be damaged.
MC
NFB
R/L11
FR-CVL
S/L21
T/L31
R2/L12
S2/L22
T2/L32
R2/L1
S2/L2
T2/L3
R/L11
S/L21
T/MC1
P/L+
N/L-
RES
SD
SD
P24
SE
RDYB
RS0
A
B
C
R/L1
S/L2
T/L3
R1/L11
S1/L21
P/+
N/-
PC
SD
X10 (MRS)
RES
SD
FR-A720
U
V
W
IM
 
(Note 1)
R/L1
S/L2
T/L3
R1/L11
S1/L21
P/+
N/-
X10 (MRS)
RES
SD
FR-A720
U
V
W
IM
R/L1
S/L2
T/L3
R1/L11
S1/L21
P/+
N/-
X10 (MRS)
RES
SD
FR-A720
U
V
W
IM
(Note 3)
FR-CV
RDYA
3-phase
AC power supply
Open collector
outputs
(Note 1)
(Note 3)
(Note 1)
(Note 3)
Main circuit terminal
Control circuit input terminal
Control circuit output terminal
R
S
T
 (Note 4)
 (Note 4)
 (Note 5)
(Note 2)
(Note 7)
(Note 2)
(Note 7)
(Note 2)
(Note 7)
Note : 1. Never connect a power supply to the inverter terminals R, S, T. 
               Such a connection, even if accidental, will damage the inverter 
               and power regeneration common converter. 
           2. Match the polarities of the P and N terminals by connecting 
               terminal P of the inverter to terminal P of the power 
               regeneration common converter and terminal N of the inverter 
               to terminal N of the power regeneration common converter as 
               shown in the connection example. Incorrect matching of 
               the polarities of the P and N terminals will result in damage 
               to the inverter.
               Do not remove a jumper across terminal P/+ and P1.
          3.  For the FR-A700, F700, A500, F500 and V500 series, remove 
               the jumpers across terminals R-R1 and S-S1, and connect 
               power supply to terminals R1, S1 for the control circuit. For the 
               FR-E700, D700, E500, S500, C500 and F500J series, the 
               inverter does not have terminals R1, S1. So you do not need to 
               make this connection. 
          4.  When wiring the dedicated stand-alone reactor and power 
               regeneration common converter as well as when wiring 
               the power supply and terminals R/L11, S/L21, T/MC1, strictly 
               observe the wiring order as shown in the connection example 
               (match phase sequence of the power supply). 
               A wrong connection will damage the power regeneration 
               common converter. 
               Do not insert an MCCB nor MC. The power regeneration 
               common converter functions abnormally. 
          5.  Make sure terminals R/L11, S/L21, T/MC1 are connected to 
               the power supply. Running the inverter without connecting 
               these terminals will damage the power regeneration common 
               converter. 
          6.  Since power to the inverter is supplied by terminals P and N, 
               set Pr.30 to 2 (for use with a high power factor converter, power 
               regeneration common converter) for the FR-A700, F700, A500, 
               F500 and V500 series. This setting disables the built-in brake 
               resistor. 
          7.  For the FR-A700, F700, E700, D700, A500, F500 and V500 
               series inverter, assign the X10 signal to any of input terminals to 
               use the inverter. 
          8.  You can connect up to six inverters to one power regeneration 
               common converter. 
          9.  Use sink logic (factory setting) when the FR-CV is connected. 
               The FR-CV cannot be connected when source logic is selected.
CAUTION