Precautions for Maintenance and Inspection
3.2.8
Measurement of main circuit voltages, currents and power
z
Measurement of voltages and currents
When instruments for commercial frequency are used for measurement, measure the following circuits using the
instruments given below.
When installing measuring instruments etc. on the output side of the power regeneration common converter,
choose the measuring instruments that have allowance in current rating since they may generate heat under the
influence of line-to-line leakage currents if the wiring distance between the power regeneration common converter
and inverter is long.
The DC voltage, which is developed across the terminals P/L+ and N/L- of the power regeneration common
converter, can be measured with a moving-coil instrument (tester). Though it varies with the power supply voltage,
the voltage will reduce under load.
< Typical Measuring Points and Instruments >
z
Classification and application by the operation principles of electrical indicator 
instruments
Measuring Points and Instruments
Type
Symbol
Principle
Indication
Applicable 
Instrument
Features
Moving-coil type
Utilizes the force that 
works between the 
magnetic field of the 
permanent magnet and the 
current flowing in the 
moving coil.
DC
(Average 
value)
Voltmeter, 
ammeter, 
resistance 
meter, 
thermometer, 
flux meter, 
rotating meter
High in sensitivity and most often 
used. Affected little by consumed 
power and external magnetic field.
Moving-iron type
Utilizes the force that is 
produced between the 
magnetic field of the 
current flowing in the fixed 
coil and the moving iron.
AC
(Effective 
value)
Voltmeter, 
ammeter
Rigidly structured and low priced. 
Affected greatly by external 
magnetic field, frequency and 
waveform.
Electrodyn
amometer 
type
Air 
core
Utilizes the force that 
works between the 
currents flowing in two 
coils.
AC/DC
(Effective 
value)
Wattmeter, 
Voltmeter, 
ammeter
A wattmeter is graduated equally.  
Affected greatly by external 
magnetic field and large in power 
consumption. Usable as an AC/DC 
standard instrument.
Item
Measuring Point
Measuring Instrument
Remarks 
(Reference Measured Value) *
Power supply voltage V
1
Across R2/L1-S2/L2, S2/L2-
T2/L3, and T2/L3-R2/L1 
Moving-iron type AC 
voltmeter
Commercial power supply 
Within permissible AC voltage 
fluctuation (Refer to page 44)
Power supply side current 
I
1
R2/L1, S2/L2 and T2/L3 line 
currents
Moving-iron type AC 
ammeter
Au
Av
Aw
W11
W12
W13
Vu
Vv
Vw
Power regeneration
common converter
R2/L1
S2/L2
T2/L3
P/L+
N/L-
V
+
-
Dedicated
stand-alone
reactor
Power
supply
To inverter