4.2.9
Parameter copy and parameter verification
(1) Parameter copy
PCPY Setting
Description
0
Cancel
1
Copy the source parameters to the operation panel.
2
Write the parameters copied to the operation panel into the destination inverter.
3
Verify parameters in the inverter and operation panel. (Refer to page 55.)
REMARKS
· When the copy destination inverter is not the FR-A701 series or parameter copy write is performed after parameter copy read is
stopped, "model error (
)" is displayed.
· Refer to the
 
parameter list on page 103 and later for availability of parameter copy.
· When the power is turned OFF or an operation panel is disconnected, etc. during parameter copy write, perform write again or
check the values by parameter verification.
· Initial settings of certain parameters are different for different capacities, so some parameter settings may be automatically
changed when parameter copy is performed from a different-capacity inverter. After performing a parameter copy from a
different-capacity inverter, check the parameter settings. (Refer to the parameter list (page 103) for the parameters with different
initial settings for different capacities.)
Parameter settings can be copied to multiple inverters.
1.
Connect the operation panel to the 
     copy source inverter.
    
• Connect it during a stop.
Display
Operation
2.
Press         to choose the parameter 
    setting mode.
Flicker ··· Parameter copy complete!!
6.
Press        to copy the source parameters 
     to the operation panel.
4.
Press    to to read the currently set value.
     "    "(initial value) appears.
Flicker ··· Parameter copy complete!!
9.
Press        to write the parameters copied to 
      the operation panel to the destination inverter.
3.
Turn        until               (parameter copy)
     appears.
5.
Turn        to change it to the setting value 
     "   ".
Flickers for about 30s
The frequency flickers
 for about 30s
About 30s later
10.
When copy is completed, 
        "     " and "             " flicker.
11.
After writing the parameter values to the copy 
        destination inverter, always reset the inverter, 
        e.g. switch power OFF once, before starting operation.