Mitsubishi Electronics FR-A701 ユーザーズマニュアル

ページ / 259
86
4.4.3
Setting the frequency by switches (three-speed setting) 
[Connection diagram]
POINT
· Use the operation panel (FR-DU07) (
 or 
) to give a start command.
· Switch ON the RH, RM, or RL signal to give a frequency command. (Three-speed setting)
· Set "4" (External/PU combined operation mode 2) in Pr. 79 Operation mode selection.
Operation example Operation at low speed (10Hz)
ON
ON
ON
Output frequency (Hz)
Speed 1
(High speed)
Speed 2
(Middle speed)
Speed 3
(Low speed)
RH
RM
RL
Inverter
High speed
Middle speed
Low speed
SD
RH
RM
RL
Operation panel
(FR-DU07)
Display
Operation
Flicker ··· Parameter setting complete!!
The parameter number 
read previously appears.
1. 
Screen at power-ON 
The monitor display appears.
2. 
Press        to choose the parameter setting 
mode.
3. 
Turn         until              (
Pr. 79) appears.
4. 
Press        to read the present set value. 
"    "(initial value) appears.
5. 
Turn         to change it to the
     setting value "    ".
6. 
Press        to set.
7. 
Mode/monitor check 
Press        twice to change to monitor / 
frequency monitor. 
[PU] indicator and [EXT] indicator are lit.
8. 
Start 
Turn ON the low-speed switch (RL). 
Middle speed
Low speed
High speed
ON