DEFINITY Enterprise Communications Server Release 6
Installation and Test for Compact Modular Cabinets  
555-230-128  
Issue 3
May 1998
Install and Cable the Cabinets 
Page 1-42
Install and Set Up the Management Terminal 
1
Install and Set Up the Management 
Terminal
To prevent unnecessary trouble tickets, do not enable the system alarms (Alarm 
Origination feature) before completing all installation and administration 
procedures.
1. Remove and retain the installation and usage instructions from the carton. 
These instructions are needed to set up the terminal after installation. See 
2. Locate the management terminal within 50 feet (15.2 m) of the system. It 
may be necessary to reduce the maximum distance limitation if higher 
gauge wire is used or if the capacitive load on the line is increased. 
3. Connect the supplied 25-pin DTE management terminal cable (H600-426) 
into the TERM connector (J3) on the Processor Interface Cable. See 
2-7 on page 2-11
 for the pinout.
4. Connect an optional printer to either the management terminal (using the 
supplied adapter cable) or to the DCE connector (J2) on the Processor 
Interface Cable. Se
Table 2-7 on page 2-11
 for the pinout of the DCE 
connector.
5. Set the terminal power switch to the ON position when finished.