EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
74-2958—1
18
Fig. 9. Functional profile of L
ON
M
ARK
® RTU object details 
(variables not implemented in Excel 10 CVAHU
are greyed).
Environmental:
Operating Temperature: -40 to 150°F (-40 to 65.5°C).
Shipping Temperature:
-40 to 150°F (-40 to 65.5°C).
Relative Humidity:
5% to 95% noncondensing.
Vibration:
Rated V2 level compliant.
Inputs/Outputs:
The W7750A Unit supports the following hardware features:
Three 20 Kohm NTC (1000 through 150,000 ohm) or 
PT3000 (250 through 12,000 ohm) resistive analog inputs 
(one reserved for space temperature and one reserved for 
the setpoint knob).
Three dry contact digital inputs (one reserved for the 
Bypass pushbutton).
LED digital output (only for the wall module LED) 2.5V at 3 
mA.
Six 24 Vac relay digital outputs (1.5A relays rated at 7.5A 
inrush current).
The W7750B,C Units support the following hardware features:
Four 20 Kohm NTC (1000 through 150,000 ohm) or 
PT3000 (250 through 12,000 ohm) resistive analog inputs 
(one reserved for space temperature and one reserved for 
the setpoint knob).
Two 0.2 to 10 VDC or 2 to 20 mA (user selectable) analog 
inputs.
Five dry contact digital inputs (one reserved for the Bypass 
pushbutton).
Eight on the W7750B (five on the W7750C) 24 Vac Triac 
digital outputs (500 mA MAX). The W7750C Unit also 
supports three 4 to 20 mA analog outputs.
LED digital output (only for the wall module LED, T7770 
models or LCD, T7560A,B) 2.5V at 3 mA.
One 20 Vdc power supply for auxiliary devices with a 
maximum current of 50 mA.
ANALOG INPUTS:
NOTE:
Only one of each type of input is allowed. For 
example, only one Outdoor Air Temperature sensor 
is allowed. No duplicate Outdoor Air Temperature 
sensors are usable on the same controller.
Space Temperature:
Type: RTD.
Supported Sensors: T7770A,B,C,D; T7560A,B.
Discharge Air Temperature:
Type: RTD.
Supported Sensors: C7100A1015*, C7770A1006, 
C7031B1033, C7031C1031, C7031D1062, C7031F1018 
(W7750B,C only), C7031J1050, C7031K1017.
Outdoor Air Temperature:
Type: RTD.
Supported Sensors: C7170A1002.
Return Air Temperature:
Type: RTD.
Supported Sensors: C7100A1015*, C7770A1006, 
C7031B1033, C7031C1031, C7031D1062, C7031F1018 
(W7750B,C only), C7031J1050, C7031K1017.
*The PT3000 sensor is not recommended for floating control 
(real time - discharge or return configured as space sensor). 
The PT3000 sensor is intended for monitoring or differential 
(staged) control
Hardware
Output
Roof Top Unit
 Controller number 8030
Mandatory
 Network
Variables
Manufacturer
Defined
Section
Optional
Network
Variables
nv9
nviOutsideRH
SNVT_lev_percent
nv8
nviOutsideTemp
SNVT_ temp_p
nv7
nviSetPtOffset
SNVT_ temp_p
nv6
nviOccCmd
SNVT_occupancy
nv5
nviApplicMode
SNVT_hvac_mode
nv16
nvoCO 2
SNVT_ppm
nv12
nvoOutsideRH
SNVT_ lev_percent
nv11
nvoOutsideTemp
SNVT_ temp_p
nv10
nvoEffectSetPt
SNVT_ temp_p
nv2
nviSetPoint
SNVT_temp_p
nv1
nviSpaceTemp
SNVT_temp_p
nv4
nvoUnitStatus
SNVT_hvac_status
nv3
nvoSpaceTemp
SNVT_ temp_p
nv13
nviSpaceRH
SNVT_ lev_percent
nv14
nviCO2
SNVT_ppm
Hardware
Input
nc42 - CO 2Limit
nc49 - Send Heartbeat
(mandatory)
nc60 - Occupancy Temperature Setpoints
(optional)
nc48 - Maximum Receive Time
nc17 - Location
(mandatory)
(optional)
(mandatory)
Configuration Properties
nv15
nviEmergCmd
SNVT_hvac_emerg
M11580