Mitsubishi Electronics FX3U-CF-ADP ユーザーズマニュアル

ページ / 124
8 CF-ADP Applied Instructions Explanation
8.1 CF-ADP Instructions types
46
FX
3U
-CF-ADP User's Manual
8.
CF-ADP Applied Instructions Explanation
This chapter explains applied instructions for the CF-ADP.
8.1
CF-ADP Instructions types
The PLC and the CF-ADP transfer data to each other using applied instructions for the CF-ADP.
Six applied instructions are provided for purpose including file creation, data writing and data reading.
• List of applied instructions for the CF-ADP
8.2
Common Items in CF-ADP Instructions
8.2.1
Function and operation
1. Processing start timing
When the command input turns from OFF to ON, the PLC starts processing for the CF-ADP.
If the command input turns OFF during processing for the CF-ADP, execution of the instruction is cancelled
and the instruction is terminated abnormally.
If the command input remains ON, the PLC executes processing repeatedly.
2. Cautions on programming
For processing for the CF-ADP, keep ON the command input for an applied instruction for the CF-ADP ON
until processing has been completed.
Make such a program that the command input is set to OFF using the instruction executing complete flag
(M8029) after all processing for the CF-ADP are finished.
Program Example
3. Instruction execution complete flag (M8029)
When processing for the CF-ADP has been completed normally, the instruction execute complete flag
(M8029) turns ON, and remains ON for one scan.
FNC No.
instruction
Description
Control direction
Detailed 
explanation
300
FLCRT
File create / check
PLC
CF-ADP
Section 8.3
301
FLDEL
File delete / CF card format
PLC
CF-ADP
Section 8.4
302
FLWR
Data write
PLC
CF-ADP
Section 8.5
303
FLRD
Data read
PLC
CF-ADP
Section 8.6
304
FLCMD
FX
3U
-CF-ADP command
PLC
CF-ADP
Section 8.7
305
FLSTRD
FX
3U
-CF-ADP status read 
PLC
CF-ADP
Section 8.8
X001
SET
M0
Command is latched
RST
M0
M8029
Instruction execution
complete
**
**
FNC 305
FLSTRD
**
M0
Processing is executed
Command is reset
Command
input
RST
M0
M8329
Instruction execution
abnormal end