BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS
63-4523—02
14
BACNET OBJECTS SUPPORTED
Device Objects
Table 4. Device Objects
Object Name
Type and 
Instance
Object Property
Thermostat Parameter
TB76xxX5x14B
Device
Object_Identifier
Property 75 (R,W)
Unique ID number of a device on a network
Object_Name
Property 77 (R,W)
Unique name of a Device on a network
Model Name
Property 70 (R)
Thermostat Model number
Firmware Revision
Property 44 (R)
Current BACnet firmware revision used by the 
thermostat
Protocol Version
Property 98 (R)
Current BACnet firmware protocol version
Default is Version 1
Protocol Revision
Property 139 (R)
Current BACnet firmware protocol revision
Default is Version 2
Max ADPU Length
Property 62 (R)
Maximum ADPU Length accepted
Default is 244
ADPU Timeout
Property 10 (R)
ADPU timeout value
Default is60 000 ms
Application-Software-
Version
Property 12 (R)
Thermostat base application software version
Default is based on current released version
Max_Master (R,W)
Maximum master devices allowed to be part of the 
network. 0 to 127, default is 127
MS/TP_Address 
Property 1001 (R,W)
BACnet MS-TP MAC Address. Proprietary attribute. 
Default is as assigned by configuration
MS/TP_Baud_Rate 
Property 1002 (R,W)
BACnet MS-TP Baud-Rate. Proprietary attribute.
Range is: 1 = 9.6 KBps, 2 = 19.2 KBps, 3 = 38.4 KBps, 4 
= 76.8 KBps and 5 = Auto Baud Rate. Index 5 is Write 
only. Reading attribute will state current Baud rate used. 
Writing index 1 to 4 will fix the Baud rate to the desired 
value.