  If PWR LED does not come on and LA and LB don’t flash, call or email ProtoCessor support 
support@ProtoCessor.com.  
  If PWR LED does not come on but the LA and LB flash, then the PWR LED is broken.  
  If LA and LB don’t start to flash there could be a problem with the ProtoCessor and you need to 
contact support@ProtoCessor.com.  
  If GP105 never comes on then you need to contact ProtoCessor support.  
  If TX and or RX don’t flash, it may represent a problem with the field wiring or Configuration 
problems in the ProtoCessor on field side or incorrect polling parameters (such as COMM 
properties like baud, parity, and etc).  
 
  The Gateway is unable to find one or more controls in the RS485 network. The individual 
controls may not be programmed with the correct and unique node address. See the respective 
control manual for details. 
  The Gateway has no communication with the controls in the RS485 network. Check the RS485 
wiring for correct wiring method. See page 2 of this manual for details. 
 
 