APC Switched Rack PDU AP8653 ユーザーズマニュアル

製品コード
AP8653
ページ / 18
Switched Rack Power Distribution Unit (AP8653)
TRIPPED
TRIPPED
pdu0558a
Network
  Main 
Menu
Sc
roll
Selec
t
In
Serial
USB
Out
T
emp/Humidity
10
/
100
x
Reset
  W
arning
  OK
  Overload
By
 El
e
c
t
r
i
c
Sch
ei
der
 
Rack PDU
Network
  Main 
Menu
Scroll
Select
In
Serial
USB
Out
T
emp/Humidity
10
/
100
x
Reset
  W
arning
  OK
  Overload
By
 E
le
c
t
r
i
c
Sc
he
i
d
e
r
 
Rack PDU
Overview and Specifications
Overview
The APC by Schneider Electric Switched Rack 
Power Distribution Unit (PDU) distributes power 
to devices in a rack. The PDU measures total load 
plus phase, bank, and outlet load. In addition, 
configured users can control the state of the 
outlets. You can access the PDU through Web, 
Telnet, SNMP, SSH, or InfraStruxure
®
 Central 
interfaces for comprehensive control and 
monitoring functionality.
Outlets. 
The Rack PDU has twenty-one (21) 
IEC-320-C13 and three (3) IEC-320-C19 locking 
outlets 2. (The locking feature is compatible with 
APC locking input cords and APC locking jumper 
cords.)
Overcurrent protection.  
The Rack PDU has 
two (2) 16 A, 1-pole hydraulic-magnetic circuit 
breakers 1.
Display interface. 
The liquid crystal display 
(LCD) 3 and input buttons 4 allow you to 
monitor current, power, and voltage 
measurements of the Rack PDU. Local 
communication can be established through the 
serial port 8, and remote communication through 
the network port 5. The USB 9 port allows for 
firmware upgrades, and the CAN 7 ports enable 
data transfer for future expansion options. The 
environmental sensor port 6 allows for 
monitoring of the temperature and humidity of the 
room or enclosure.
Power cord. 
The 3.0-m (10-ft) power cord 
terminates with a 32 A, 3-pin IEC-309 
connector :.
Toolless mounting. 
The Rack PDU has two 
toolless mounting pegs ; for 0 U mounting 
capability in a rack or enclosure.