Operation
Operating Instructions
Background Music
When background music option is enabled via S5 DIP switch 3, the ACC-25/50 will constantly 
monitor the external audio input RCA Jack.  Both amplifiers and speaker wiring continue to be 
fully supervised when background
*
 music is output from the ACC-25/50.  Amplifier faults are 
reported after 75 seconds.  Note that when AC power is lost, the ACC-25/50 will shut off 
background music to conserve batteries.  
*
Note that the Local Authority Having Jurisdiction must approve the use of background music.
*
Background music is not available with the ACC-25/50ZS or ACC-25/50ZST
Amplifier Fault
Both amplifiers are constantly monitored for proper functionality.  Should either amplifier fail, 
the AMP SUPV LED will turn off and the Circuit Trouble LED will turn on.  When the system 
is configured for backup, failure of the primary amplifier will cause the backup amplifier to be 
switched in.
NAC (Speaker) Output
The wiring to each amplifier is supervised for opens and shorts at all times in standby and 
while in alarm or when background music
*
 is enabled.  A wiring fault will cause the circuit 
Trouble LED located on each amplifier module to turn on.  It should be noted that the green 
AMP SUPV LED may remain on for wiring faults.
The ACC-ZSM wiring to each speaker circuit is supervised for opens and shorts in standby and 
for shorts while in alarm.  A wiring fault will cause the zone/circuit Trouble LED on the ACC-
ZPMK corresponding to the affected circuit to turn on.
*
Note that the Local Authority Having Jurisdiction must approve the use of background music.
*
Background music is not available with the ACC-25/50ZS or ACC-25/50ZST
ACC-ZPMK Zone Page Module
The ACS wiring between the ACC-ZPMK and FACP is supervised.  A loss of communication 
on the ACS (EIA-485) link will cause the FACP Trouble LED to light on the ACC-ZPMK 
module.
The ribbon cable between the ACC-ZPMK and audio panel is supervised.  A loss of 
communication will cause the ACC Trouble LED to light on the ACC-ZPMK module.
Remote Microphone 
The FC-RM Remote Microphone and associated wiring are supervised for faults by the panel.  
ACC-25/50 & ACC-25/50ZS:  The Trouble LED located on the FC-MIM Microphone 
Interface Module, which is mounted in the panel, will illuminate on a trouble condition.  
ACC-25/50ZST:  The Remote Microphone Trouble LED located on the ACC-FFT keypad will 
illuminate on a trouble condition.  Refer to the FC-RM Product Installation Document #51247 
for a description of possible fault conditions
Power ON LED
The loss of primary (AC) and secondary (battery) power will extinguish the Power ON LED.
Internal Power Supplies
Power fed to the amplifiers from the main circuit board is fully supervised.  Should standby or 
alarm power feeds to either amplifier fail, the unit will go into trouble. Note that a power 