Siemens bacnet 125-5037 ユーザーズマニュアル

ページ / 48
Product Overview 
4 
 
Siemens Building Technologies, Inc. 
 
 
Communication Wiring 
The controller connects to the field panel by means of a Floor Level Network (FLN) 
trunk. Communication wiring connects to the three screw terminals on the controller 
labeled “+” (positive), “-“(negative), and “S” (Shield) (Figure 3). 
FLN TRUNK
+ -
(SHIELD)
(SHIELD)
(+)
(+)
(-)
(-)
TEC05XXR1
 
TEC0516R2
Wirenut
120 ohm
½ W
120 ohm
½ W
Note: = System Common
e to earth
Terminator 
3-Wire Network Interface
+
-
+
-
+
-
NOTE: When wiring a 3-wire system to a 2-wire system see 
the Wiring Guidelines Manual (125-3002) for detailed information. 
 
Figure 3.  Communication Wiring (2-wire). 
Figure 4.  Communication Wiring (3-wire). 
Controller LED Indicators 
The controller has seven Light Emitting Diode (LED) indicators (see Figure 1). 
Table 2.  Controller LEDs. 
LED Type 
Label  
(if present)* 
LED 
Number 
Indication 
DO 
LED 3 - LED 6 
3 - 6 
Indicates the ON/OFF status of the DO 
associated with it. A glowing LED indicates that 
the DO is energized. 
Transmit 
TX 
Indicates, when flashing, that the controller is 
transmitting information to the field panel. 
Receive 
RX 
Indicates, when flashing, that the controller is 
receiving information from the field panel. 
BST 
”Basic Sanity Test” 
BST 
Indicates, when flashing ON and OFF once per 
second, that the controller is functioning 
properly. 
* Some LED labels and numerals may be hidden by the controller cover. 
Temperature Sensors 
Room Temperature Sensor  
The controller room temperature sensor connects to the controller by means of a 
cable terminated at both ends with a six-conductor RJ-11 plug-in connector.