PVI Industries PV 500-6 ユーザーズマニュアル

ページ / 14
DURAWATT
® 
ELECTRIC WATER HEATER 
 
PV500-6   09/07
 
12
 
 
 
 
 
   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
NOTE: Elements are 
usually
 wired to contactors in groups, in order to maintain an amperage draw of close to, but not more 
than, 50 amps per contactor.  
 
 
*Applications for 600V use a re-rated 480V element.  Therefore, the 40W/in.
is rated for 14 kW instead of 9 kW. 
 
 
  
KW-VOLTAGE 
Ø AMPS PER ELEMENT 
Ø AMPS PER ELEMENT 
AMPS PER LEG 
AMPS TOTAL 
AMPS PER LEG 
AMPS TOTAL 
*14 kW-600V 
13 1/2 
13 1/2 
— 
— 
*7 kW-600V 
— 
— 
18 kW-480V 
22 
22 
— 
— 
9 kW-480V 
11 
11 
— 
— 
4.5 kW-480V 
5 1/2 
5 1/2 
— 
— 
18 
kW-240V 
44 44 25 75 
kW-240V 
22 22 13 38 
4.5 
kW-240V 
11 11 6 18 
18 
kW-208V 
50 50 29 87 
kW-208V 
25 25 15 44 
4.5 kW-208V 
12 1/2 
12 1/2 
22 
TABLE 2 
TYPICAL CURRENT MEASUREMENT 
FIGURE 11 
FIGURE 12