page 42 — DCa150USJ2 60 hz generator • operation anD partS manUal — rev. #0 (08/22/11) 
generatOr Outputs
generator oUtpUt voltageS 
A wide range of voltages are available to supply voltage for 
many different applications. Voltages are selected by using 
the 
voltage selector switch (Figure 14). To obtain some of 
the voltages as listed in Table 7 (see below) will require a 
fine adjustment using the 
voltage regulator (VR) control 
knob located on the control panel. 
voltage Selector Switch
The voltage selector switch (Figure 14) is located above 
the output terminal panel’s Hard Wire Hook-up Panel. It 
has been provided for ease of voltage selection.
Figure 14. Voltage Selector Switch
voltage Selector Switch locking Button
The voltage selector switch has a locking button to protect 
the  generator  and  load  from  being  switched  while  the 
engine is running. To lock the voltage selector switch, press 
and hold  the red button located at the bottom of the switch.
  CaUtion
never change the position of the voltage selector 
switch while the engine is running. alWaYS place 
circuit  breaker  in  the 
OFF position  before  selecting 
voltage
.
table 7. voltages available
UvWo output 
terminal lugs
voltage Selector Switch
3-phase 240/139v position
voltage Selector Switch
3-phase 480/270v position
 
line-line
208V
220V
240V
416V
440V
480V
1Ø 
line-neutral
120V
127V
139V
240V
254V
277V
voltage Selector Switch Single-phase 240/120v position
1Ø 
line-neutral/
line-line
120V 
Line-Neutral
N/A
N/A
240V 
Line-Line
N/A
N/A
Generator Amperage
Table  8  shows  the 
maximum  amps  the  generator  can 
provide. 
DO NOT exceed the maximum amps as listed..
gFCi receptacle load Capability
The  load  capability  of  the  GFCI  receptacles  is  directly 
related to the voltage being supplied at either the output 
terminals or the 2 twist lock auxiliary receptacles.
Table  9  and Table  10  show  what  amount  of  current  is 
available at the GFCI receptacles when the output terminals 
and twist lock receptacles are in use. Be careful that your 
load does not to exceed the available current capability at 
the receptacles.
table 8. generator maximum amps
rated voltage
maximum amps
1Ø 120 Volt
333.3 amps (4 wire)
1Ø 240 Volt
166.7 amps (4 wire)
3Ø 240 Volt
361 amps
3Ø 480 Volt
180 amps
table 9.  1Ø gFCi receptacle load Capacity
KW in Use 
twist lock (C6369)
available load 
Current (amps)
1Ø 240/120V
GFCI Duplex 
5-20R 120V
87.0
0
85.8
5 amps/receptacle
84.6
10 amps/receptacle
83.4
15 amps/receptacle
82.2
20 amps/receptacle
Table 10.  3Ø gFCi receptacle load Capacity
Kva in Use 
(UvWo terminals)
available load 
Current (amps)
3Ø 240/480V
GFCI Duplex 
5-20R 120V
150
0 amps/receptacle
146
5 amps/receptacle
142
10 amps/receptacle
138
15 amps/receptacle
133
20 amps/receptacle