page 52 — DCa150USJ2 60 hz generator • operation anD partS manUal — rev. #0 (08/22/11) 
generatOr shut-dOWn prOcedures
normal ShUtDoWn proCeDUre
To shutdown the generator, use the following procedure:
1.  Place both the 
main, gFCi and loaD circuit breakers 
as shown in Figure 54 to the 
OFF position..
Figure 54. Main, GFCI and Load 
Circuit Breakers Off
2.  Place the engine speed switch (Figure 55) in the “
loW” 
(down) position..
Figure 55. Engine Switch (Normal)
3.  Let the engine cool by running it at low speed for 3-5 
minutes with no load applied.
4.  Place the 
mpeC Control Switch (Figure 56) to the 
oFF/reSet position.
Figure 56. MPEC Control Switch (Off/Reset)
5.  Verify that 
all status LEDs on the MPEC display are 
OFF (not lit). 
6.  Remove all loads from the generator.
7.  Inspect entire generator for any damage or loosening 
of  components  that  may  have  occurred  during 
operation.
emergenCY ShUtDoWn proCeDUre
1.  Place the 
mpeC Control Switch (Figure 56) in the 
oFF/reSet position.
12.  The
 tachometer gauge (Figure 51) will indicate the 
speed of the engine when the generator is operating. 
Under  normal  operating  conditions  this  speed  is 
approximately 1800 RPM’s.
Figure 51. Engine Tachometer Gauge
13.  Place the 
main, gFCi, and aux. circuit breakers in the 
ON position (Figure 52).
Figure 52. Main, Aux. and GFCI  
Circuit Breakers (ON)
14.  Observe  the  generator’s  ammeter  (Figure  53)  and 
verify it reads the anticipated amount of current with 
respect to the load. The ammeter will only display a 
current reading if a load is in use.
Figure 53. Ammeter (Load)
15.  The generator will run until manually stopped or an 
abnormal condition occurs.
  Warning
never  stop  the  engine  suddenly  except  in  an 
emergency.