Installation 
Electrical Installation 
Revision 6 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
17 
7/07  
 
 
Electrical Installation 
General Wiring Recommendations 
 
 
 
Only qualified personnel should perform wiring. 
Wiring must conform to national and local electrical codes. 
 
 
In general, copper wire used. Unless locally applicable codes dictate otherwise, the recommended minimum 
wire sizes in Table 2 should be observed. 
 
Table 2 Recommended Minimum Wire Size 
 
AWG 
Description 
14 
Earth ground wire to common power supply. 
18 
Earth ground wire to single actuator. 120/240 V ac line leads. +24 V and common 
signal leads. Common signal leads, relays, and aux switches. 
 
Safety Precautions 
 
 
An external disconnect switch must be installed to break all current carrying 
conductors connected to the actuator. Turn off power before working on 
conductors. Failure to observe this precaution may result in serious personal injury. 
 
Actuator Connections  
 
 
 
ATTENTION 
The ground terminal must be connected to a reliable earth ground. 
 
 
 
While the unit is powered, a potentially lethal shock hazard exists inside the case. 
Do not open the case while the unit is powered. Do not access the terminals while 
the unit is powered. 
 
 
The actuator terminal connections for the field wiring are located behind the cover on the actuator case as 
shown in Figure 2. Power and field wiring is brought into the actuator through two access holes located on the 
side of the actuator case.   
 
Use both openings: one for low level wiring (control signal) and the other for high 
level wiring (120Vac).  
Do not run both the High Level and Low Level wiring through the same 
opening.
 
The screw terminals, locations, and descriptions for all customer connections are identified in the tables and 
figures that follow.