Honeywell commercialpro tb7220 ユーザーズマニュアル

ページ / 24
TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
63-2635—03
22
TROUBLESHOOTING (TABLE 11)
Table 11. Troubleshooting.
Symptom
Possible Cause
Action
Display does not come on.
Thermostat is not being powered.
Check for 24 Vac between C and Rc.
Check that AAA batteries are installed correctly 
and are good.
Temperature settings do not 
change.
The upper or lower temperature limits were 
reached.
Check temperature setpoints.
Check ISU 0600 and 0610; modify as needed.
The keypad is fully locked.
Check ISU 0670 to change keypad locked 
options.
Heating or cooling does not come 
on.
Thermostat minimum off-time is activated. Wait up to five minutes for the system to respond.
System selection is not set to Heat or Cool. Set system Selection to correct position.
System type Selection is incorrect.
Check ISU 0170 and make sure correct System 
type is chosen.
Thermostat is calling for Heat 
(Heat on) or Cool (Cool on) but 
no heating or cooling is running.
Heating or cooling equipment is not 
operating.
Check wiring.
Check ISU 0170 and make sure correct system 
type is chosen.
Verify operation of equipment in System Test 
mode.
Heat does not turn on (Heat On is 
solid in the display).
Heating equipment failure.
Check for 24 Vac at the equipment on the 
secondary side of the transformer between power 
and common. If voltage is not present, check the 
heating equipment to find the cause of the 
problem.
Check for 24 Vac between the heat terminal (W) 
and transformer common. If 24 Vac is present, the 
thermostat is functional. Check the heating 
equipment to find the cause of the problem.
Loose or broken wire connection between 
thermostat and heating equipment.
Check for 24 Vac between the heat terminal (W) 
and transformer common. If voltage is not 
present, check wire connection (loose or broken) 
between the thermostat and the heating 
equipment.
Cooling does not turn on (Cool 
On is solid in the display).
Cooling equipment failure.
Check for 24 Vac at the equipment on the 
secondary side of the transformer between power 
and common. If voltage is not present, check the 
cooling equipment to find the cause of the 
problem.
Check for 24 Vac between the cool terminal (Y) 
and transformer common. If 24 Vac is present, the 
thermostat is functional. Check the cooling 
equipment to find the cause of the problem. 
Loose or broken wire connection between 
thermostat and cooling equipment.
Check for 24 Vac between the cool terminal (Y) 
and transformer common. If voltage is not 
present, check the wire connection (loose or 
broken) between the thermostat and the cooling 
equipment.
Fan does not turn on in a call for 
heat (electric furnace).
Fan Control in Heating is set to Gas or Oil 
Furnace (Setting 0180).
Set Fan Control in Heating to Electric Furnace 
(Setting 0180).
Heat pump puts out cool air in the 
heat mode and warm air in the 
cool mode.
Changeover Valve (ISU 0190) is not 
configured to match the changeover 
required by the installed heat pump.
Set Changeover Valve (ISU 0190) to match the 
changeover required by the installed heat pump.
Both the heating and cooling 
equipment are running at the 
same time.
The heating equipment is not a heat pump 
but the System Type (ISU 0170) is set to 
Heat Pump.
Set System Type (ISU 0170) to match the 
installed heating and/or cooling equipment.
Heating and cooling wires are shorted 
together.
Separate the shorted heating and cooling wires.