T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
23
63-4355—4
CROSS REFERENCE
All T7300/Q7300 Series 2000 models are different from the existing T7300/Q7300 T8611 and T8621 devices as summarized in 
Table 14.
Temperature settings 
change from original 
setting.
Trying to set heat and cooling setpoints 
too close together. Automatic changeover 
thermostat models have a deadband. 
Example: cool setpoint: 72, deadband: 3, 
heat setpoint: 68; changing heat setpoint 
to 70 automatically changes cool setpoint 
to 73.
Check that the heating setpoint is lower than the 
cooling setpoint.
Check Installer Setup number 30 to identify the 
deadband between heating and cooling setpoints. 
Reconfigure if desired.
Room temperature is out 
of control.
Remote temperature sensing is not 
working.
Checkout all remote sensors.
Heating will not come on. No power to the thermostat.
Check that X terminal is connected to the system 
transformer.
Check for 24 Vac between X and R or RH terminals.
— If missing 24 Vac:
— check if the circuit breaker is tripped; if so, reset 
the circuit breaker.
— check if the system fuse is blown; if so, replace 
the fuse.
— check if the HVAC equipment power switch on 
the is in the Off position; if so, set to the On 
position.
— check wiring between thermostat and HVAC 
equipment and replace any broken wires and 
tighten any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
Heating will not come on 
(Continued).
Thermostat minimum off time is activated 
and wait indicator is displayed.
Wait up to five minutes for the system to respond.
Enter Installer Setup number 38. Reconfigure 
minimum off time (if required).
System selection is not set to Heat.
Set system selection to Heat.
Cooling will not come on. No power to the thermostat.
Check that X terminal is connected to the system 
transformer.
Check for 24 Vac between X and R or RC terminals.
— If missing 24 Vac:
— check if the circuit breaker is tripped; if so, reset 
the circuit breaker.
— check if the system fuse is blown; if so, replace 
the fuse.
— check if the HVAC equipment power switch on 
the is in the Off position; if so, set to the On 
position.
— check wiring between thermostat and HVAC 
equipment and replace any broken wires and 
tighten any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
Thermostat minimum off time is activated 
and wait indicator is displayed.
Wait up to five minutes for the system to respond.
Enter Installer Setup number 33. Reconfigure 
minimum off- time (if required).
System selection is not set to Cool.
Set system selection to Cool.
System on indicator 
(flame: heat, 
snowflake: cool) is 
displayed, but no warm 
or cool air is coming from 
the registers.
Conventional heating equipment turns on 
the fan only once the furnace has warmed 
up to a setpoint.
Wait one minute after seeing the on indicator and then 
check the registers.
Heating or cooling equipment is not 
operating.
Verify operation of heating or cooling equipment in self-
test.
Table 13. Troubleshooting Information. (Continued)
Symptom
Possible Cause
Action