Honeywell T7350 ユーザーズマニュアル

ページ / 40
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
17
63-2605—5
Using Temporary Occupied Override
The Temporary Occupied Override can be used when the 
T7350 is in Not Occupied or Standby mode. It switches to the 
Occupied mode for a fixed number of hours.
1. To use the default occupied override, press Temporary 
Occupied.
NOTE: The default temperature setting is the 
Occupied setpoint.
2. To select a temperature setting other than the default, 
press up S or down T until the desired temperature off-
set is displayed (range is 0° F to 3° F [0° TO 2° C]).
NOTE: This offset can be restricted by the limits 
detailed in the Setpoint Limits section.
Using Temporary Not Occupied Override
The Temporary Not Occupied Override fixes the device to 
operate in Not Occupied mode for a number of days (between 
1 and 99) without changing programming saved in memory.
NOTES:
If the number of days is set to zero, no temporary 
change takes effect.
If the number of days is set just below zero, the 
display for days is “---” (an indefinite override).
To turn off this override, you must press Run 
Schedule.
1. Press Temporary Not Occupied.
2. Press up S or down T to change the duration of the 
Not Occupied period (in days).
NOTE: The default temperature setting is the 
Not Occupied setpoint.
3. Press 
 to display the default setpoint.
NOTE: The only way to change this setpoint is to 
change the Not Occupied setpoint.