TROUBLESHOOTING
DISCONNECT SENSOR LEADS FROM ELECTRONIC
CONTROL MODULE AND MEASURE RESISTANCE OF 
SENSOR(S) WITH OHMMETER.
IS RESISTANCE BETWEEN 700K AND 30K OHMS 
(SEE TABLE 1)? 
SENSOR(S) OK. DISCONNECT ECO LEADS AND 
MEASURE RESISTANCE WITH OHMMETER. IS WATER 
TEMPERATURE GREATER THAN 210˚F AND ECO 
RESISTANCE LESS THAN  10 OHMS (SHORTED)?
IS THE POTENTIOMETER REMOTE?
DISCONNECT POTENTIOMETER LEADS FROM 
ELECTRONIC CONTROL MODULE. MEASURE 
RESISTANCE OF POTENTIOMETER WITH OHMMETER.
IS RESISTANCE GREATER THAN 1000 OHMS AT MINIMUM 
TEMPERATURE SETTING (CHECKS FOR SHORT)?
POTENTIOMETER OK. REPLACE ELECTRONIC CONTROL 
MODULE. RECONNECT ALL LEADS AND CHECK OUT 
SYSTEM.
SENSOR(S) MAY BE SHORTED OR OPEN.
CHECK FOR LOOSE, BROKEN OR SHORTED WIRES.
REPLACE SENSING BULB(S) IF NECESSARY. 
REPLACE SENSING BULB WITH ECO LIMIT AND 
CHECK OUT BALANCE OF SYSTEM.
REPLACE ELECTRONIC CONTROL MODULE. 
RECONNECT ALL LEADS AND CHECK OUT SYSTEM.
REPLACE POTENTIOMETER. 
RECONNECT ALL LEADS AND CHECK OUT SYSTEM. 
START
NO
YES
YES
NO
NO
NO
YES
M134B
YES
L8104A, B, C, D
Troubleshooting
If water temperature is too hot, proceed as follows: