Ideal nd2354 ユーザーズマニュアル
Mechanical Characteristics (continued)
EM IMMUNITY
EM IMMUNITY
- EN 50082-2 (1995), Industrial immunity
- EN 61000-4-2 (1995), ESD
- ENV 50140 (1993), EM Radiated field of RF
- EN 61000-4-4 (1995), EFT burst
- ENV 50141 (1993), RF common mode
- EN 61000-4-8 (1995), 50 Hz H-field
- ENV 50140 (1993), EM Radiated field of RF
- EN 61000-4-4 (1995), EFT burst
- ENV 50141 (1993), RF common mode
- EN 61000-4-8 (1995), 50 Hz H-field
- EN 50082-1 (1997), Residential Immunity
- EN 61000-4-5 (1995), Surges
- EN 61000-4-11 (1994), Dips, Interruptions.
- EN 61000-4-11 (1994), Dips, Interruptions.
(as shown in the test report reference number: 08077IEM.002)
SAFETY WARNINGS
Note that the instrument should not be operated or powered up while the cover is off. The analyzer has been designed
and tested to meet IEC 348 standard and is factory-shipped in proper conditions.
and tested to meet IEC 348 standard and is factory-shipped in proper conditions.
Maintenance
Please send units in need of repair to:
Please send units in need of repair to:
IDEAL INDUSTRIES, INC.
Becker Place
Sycamore, Illinois 60178
Becker Place
Sycamore, Illinois 60178
Technical Service
Please call our toll free technical support hotline at 800-435-0705 for any questions, or check out our website at
www.testersandmeters.com
Please call our toll free technical support hotline at 800-435-0705 for any questions, or check out our website at
www.testersandmeters.com
19
Technical Specifications
Supply voltage:
Through an external power supplier set 120 VAC (+10% / -15%)
Frequency:
Supply voltage:
Through an external power supplier set 120 VAC (+10% / -15%)
Frequency:
50...60 Hz
Burden:
8 VA
Operation temperature: 0 / 50 ºC
Measuring circuit:
Measuring circuit:
THREE PHASE, ARON
Safety:
Category II - 600 V, as per EN 61010
Voltage measurement
Measuring range:
Measuring range:
20 to 500 V a.c. (phase-neutral)
20 to 866 V a.c. (between phases) automatic scale adjustment
20 to 866 V a.c. (between phases) automatic scale adjustment
Other voltages:
through suitable voltage transformers
Frequency:
45 to 65 Hz
Current measurement
Measuring range:
Measuring range:
see available current clamps
Current transducer ratio: user-programmable
Measurement units:
Measurement units:
automatic scale adjustment
Built-in clock with rechargeable battery: Date and time
Display:
LCD; 160 x 160 pixels
RS-232 output:
serial type output
Internal memory:
256 kbytes or 1 Mb according to the model
Accuracy
Voltage:
Voltage:
0.5 % of readout ± 2 digits
Current
0.5 % of readout ± 2 digits
Active power
1.0 % of readout ± 2 digits
Reactive power
1.0 % of readout ± 2 digits
Measuring conditions to assure accuracy class:
- Errors due to voltage and current transformer not included
- Temperature range:
- Errors due to voltage and current transformer not included
- Temperature range:
5 ºC to 45 ºC
- Power factor:
0.5 to 1
- Measuring rang:
between 5 % and 100 %
Mechanical Characteristics
Case:
Case:
Portable case.
Dimensions:
220 x 60 x 130 mm
Connection terminals:
input/output terminals
Keyboard/ display:
in frontal panel
Weight:
0,8 kg.
RELEVANT STANDARDS
EN 60664,EN 610110, EN 61036, VDE 110, UL 94
EN 60664,EN 610110, EN 61036, VDE 110, UL 94
EM EMISSION
- EN 61000-3-2 (1995), Harmonics
- EN 61000-3-3 (1995), Fluctuations de tensión
- EN 50081-2 (1993), Industrial emission
- EN 55011 (1994): Conducted (EN 55022 - Clase B)
- EN 55011 (1994): Radiated (EN 55022 - Clase A)
- EN 61000-3-3 (1995), Fluctuations de tensión
- EN 50081-2 (1993), Industrial emission
- EN 55011 (1994): Conducted (EN 55022 - Clase B)
- EN 55011 (1994): Radiated (EN 55022 - Clase A)
IDEAL INDUSTRIES, INC.
Sycamore, IL 60178, U.S.A.
800-304-3578 Customer Assistance
www.testersandmeters.com
ND 2354-2
Sycamore, IL 60178, U.S.A.
800-304-3578 Customer Assistance
www.testersandmeters.com
ND 2354-2
Made in Spain
Warning
Take into account all installation instructions referred in
sections INSTALLATION AND STARTUP, CONNECTION
INSTRUCTIONS and TECHNICAL SPECIFICATIONS OF THE
ANALYZER.
sections INSTALLATION AND STARTUP, CONNECTION
INSTRUCTIONS and TECHNICAL SPECIFICATIONS OF THE
ANALYZER.