Communication modules 
 
7.1 8xIQ-Sense 
RF 300 
System Manual, 05/2005, (4)J31069 D0166-U001-A1-7618, -- 
7-5
 
7.1.4 
Addressing 
The address range of the 8xIQ-Sense module is 16 bytes I/O.  
This is independent of the choice of channel profiles on the connected device 
(i.e. the IQ profile IDs in HW Config). 
Access to memory areas 
A direct association exists between the number of the channel to which the IQ-Sense device 
is connected (terminal) and the input and output data area of the module. Based on the 
address range, the following addresses can be used to access the memory areas: 
Address = module initial address + (channel no. x 2)