Process I/O
ET 200M distributed I/O
Closed-loop control modules
11/28
Siemens ST PCS 7 · November 2007
11
Integration
Use in SIMATIC PCS 7
The FM 355 / FM 355-2 modules can be used to implement con-
trol tasks outside the SIMATIC PCS 7 automation system. The 
modules have not only controller structures but also analog and 
digital channels, thus eliminating the need for additional mod-
ules to detect the setpoint/actual value or to control the actuator. 
On the one hand this reduces the work load for the CPU, on the 
other hand it enables backup mode with which the control sys-
tem continues to work even if the CPU fails. In this case the 
FM 355 module can be operated further with an OP operator 
panel (does not apply to FM 355-2). 
The operator panel is connected to the PROFIBUS DP fieldbus 
for this purpose. The CPU of the automation system can surren-
der input privilege to the operator panel in normal operation as 
well. The parameters that can be accessed with the operator 
panel are the setpoint and manipulated variable. If the FM 355 
module is operated from the operator panel, the automation sys-
tem reads back the values accessible from the operator panel 
after the input privilege is withdrawn or recovered again. Bump-
less continuation of the operations is thus assured. 
IM 153-2 High Feature interface modules are needed for the 
PROFIBUS DP connection when the FM 355 / FM 355-2 control-
ler modules are used in ET 200M.
PCS 7 blocks
CFC blocks with OS faceplates for all FM 355 modules are in-
cluded in the scope of supply of the standard SIMATIC PCS 7 li-
brary (part of engineering software). These blocks are integrated 
into the PCS 7 driver concept. This guarantees homogenous 
system integration (including automatic diagnostics messages).
Parameterization in HW-Config
A configuration package containing all parameterization masks 
required for configuring, parameterizing and commissioning is 
included in the scope of supply of the FM 355 controller mod-
ules.
Note
:
In the case of the FM 355 C and FM 355 S controller modules, the chan-
nels are not electrically isolated from one another
IM 153-2
OP
FM-355 module 
(80 mm wide)
Standard
modules
Automation
system
ET 200 Rack
Selection and Ordering Data
Order No.
FM 355 C controller module
With 4 analog outputs for 
4 continuous-action controllers
Required front connector: 
2 x 20-pin
Incl. multi-lingual configuration 
package, manual and Getting 
Started (German, English, 
French, Italian) on CD-ROM
6ES7 355-0VH10-0AE0
FM 355 S controller module
With 8 digital outputs for 4 step or 
pulse controllers
Required front connector: 
2 x 20-pin
Incl. multi-lingual configuration 
package, manual and Getting 
Started (German, English, 
French, Italian) on CD-ROM
6ES7 355-1VH10-0AE0
FM 355-2 C temperature con-
troller module
With 4 analog outputs for 
4 continuous-action controllers
Required front connector: 
2 x 20-pin
Incl. multi-lingual configuration 
package, manual and Getting 
Started (German, English, 
French, Italian) on CD-ROM
6ES7 355-2CH00-0AE0
FM 355-2 S temperature con-
troller module
With 8 digital outputs for 4 step or 
pulse controllers
Required front connector: 
2 x 20-pin
Incl. multi-lingual configuration 
package, manual and Getting 
Started (German, English, 
French, Italian) on CD-ROM
6ES7 355-2SH00-0AE0