Limitations of C-Bus participants 
20 
Siemens Building Technologies
 
 007836_a_en_--.doc
Fire & Security Products 
 
03.2004
 
 
Limitations of C-Bus participants 
 
This chapter describes the quantitative limits of the FC700A station. 
The selection of the station type depends on the requirements. The following vari-
ants are available: 
 
Station type 
Modules 
Flash ROM 
(2x1024Kx8Bit) 
'Program file' 
SRAM 
Soldered 
EPROM set 
RAM set 
FC700A B3Q700 CIY00760 
4x512Kx8Bit – 
– 
FT700A B3Q700 
CTY00760 
4x512Kx8Bit – 
– 
FG700A E3H020 
– 
– 
CKQ007.60 
(2x512Kx8Bit) 
2 x Z3S070 
(2x512Kx8Bit) 
(Assembly ex works)
 
8.1 
Main CPU limits 
8.1.1 
Maximum number of devices 
 
1000 devices (with AMPK=1) per FC700A. 
 
 
8.1.2 
Limits in the logical structure 
 
The limits in the logical structure are given by the node-type, by the highest possi-
ble CSX number and the maximum amount of display-digits. These limits are given 
by the system and are independent of the memory capacity. 
Table 'Limits of the logical structure' 
Maximum rating 
AREAS per STATION 
Maximum rating 
SECTIONS per AREA 
Maximum rating 
ZONES per SECTION 
Maximum rating 
ELEMENTS per ZONE
... 4 
…255 
…255 
…99 
International 5: …255 
 
8.1.3 
Maximum number of criteria in zones control 4 and 6 
 
The maximum number of control zones with 16 criteria is limited by 200. 
 
 
 
 
 
 
 
To optimize the performance of your system minimize the number of CPU-overlapping controls as 
much as possible. 
A maximum of 40 CPU-overlapping controls (zone control 6) are admissible per C-Bus. 
 
 
 
 
8.1.4 
Maximum number of ZONE time channel 
 
Max. 16 ZONES time channel are permitted per station.