Sentry Industries PT22 ユーザーズマニュアル

ページ / 74
Displaying infeed status 
The Istat or Iload command displays the status of one or more infeed.  
This display includes the infeed absolute and descriptive names and the Input Status and current Load 
reported to the Sentry by the infeed.   
To display status of one or more infeeds: 
Type istat and press Enter, or 
Type iload and press Enter
Examples 
The following command displays the infeed status: 
Sentry: istat 
   Input    Input                      Input      Input 
   Feed ID  Feed Name                  Status     Load 
   .AA      HQ_1_Infeed_A              On         10.5 Amps 
   .AB      HQ_1_Infeed_B              On          5.5 Amps 
   .AC      HQ_1_Infeed_C              On          9.0 Amps 
   .AD      HQ_1_Infeed_D              On          0.5 Amps 
Connecting to a serial device 
The Connect command allows Pass-Thru serial connection to devices attached to one of the two 
standard serial ports (Console, Modem) or a Pass-Thru port. 
To connect to a serial device: 
At the Sentry: prompt, type connect, followed by the serial port name and press Enter
Examples 
The follow command connects to the serial device connected to the Modem port: 
Sentry: connect modem<Enter> 
To disconnect from a serial device: 
 
Type !*break and press Enter
Displaying the status of the Environmental Monitor 
The Envmon command displays the status of the integrated Environmental Monitor. 
By default, only administrative user accounts are allowed access to the Envmon command.  An 
administrator may user the Set User Envmon command to enable and disable access for other user 
accounts. 
To display the status of the Environmental Monitor: 
At the Sentry: prompt, type envmon and press Enter
Example 
The following command displays the status of the Environmental Monitor. 
Sentry: envmon<Enter> 
Environmental Monitor .A 
   Name: Florida_HQ_1                  Status: Normal 
   Temperature/Humidity Sensors 
      ID    Name                       Temperature    Humidity 
      .A1   Temp_Humid_Sensor_A1       Not Found      Not Found 
      .A2   T/H2_Florida_HQ_1          23.5 Deg. C    22 % RH 
Starting a new session 
The Login command activates the Username: prompt. The current session ends, allowing a user to log 
in and start a new session under a different username. 
To start a new session: 
At the Sentry: prompt, type login and press Enter.  The Username: prompt appears.   
Sentry PT22 